Transformer protection system ur series (748 pages)
Summary of Contents for GE GFK-2741C
Page 1
Intelligent Platforms Programmable Control Products PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C March 2015...
Page 2
Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced herein.
Page 3
Contact Information If you purchased this product through an Authorized Channel Partner, please contact the seller directly. General Contact Information Online technical support and GlobalCare http://support.ge-ip.com Additional information http://www.ge-ip.com/ Solution Provider solutionprovider.ip@ge.com Technical Support If you have technical problems that cannot be resolved with the information in this guide, please contact us by telephone or email, or on the web at http://support.ge-ip.com...
This manual covers the technologies used to back up volatile memory on PACSystems RX3i and RX7i CPUs, and RXi Controllers. Other GE Intelligent Platforms manuals and documents discuss memory retention technologies in passing. However, when it comes to energy sources used by PACSystems to back up volatile memory, this manual should be considered the definitive source.
Page 7
Introduction PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
The disadvantages are that external mounting is required due to battery and charger size, no support for low battery detection, limited temperature range (0°C – 50°C), and inability to charge in a hazardous location. GFK-2741C March 2015...
For the rechargeable battery, the backup time indicated is based on each full charge. Discontinued product as of March 2015 For CPUs that do not support low battery detection, only the total retention time is provided. PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
The use of a non-smart battery or a CPU not on the above list will result in the low battery detection bits being unreliable. Low/failed battery conditions are indicated by CPU LED operation and %S status bits. For details, refer to Diagnostics in the PACSystems CPU Reference Manual, GFK-2222. GFK-2741C March 2015...
The Battery Low period of 15 days starts at Point T1, but the low battery fault is logged at Point T2, when the controller is powered ON. The user should be aware that the Low Battery fault timestamp does not indicate the start of the 15 day Battery Low period. PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
#8-32 threads, according to the hole pattern shown in the following figure. Use care to keep metal chips from falling into other equipment. Securely attach the Auxiliary Battery Module to the panel mounting surface using four #8-32 x ½” flat head machine screws. #8-32 (four places) 5.253" 133.43 mm) 1.746" (44.35 mm) GFK-2741C March 2015...
(50mm) twisted red/black 22 AWG cable with female two-pin connector compatible with the battery connector on PAC Systems CPUs. Operating temperature range 0 to +60ºC Nominal shelf life 5 years @ 20ºC without the enabling adapter cable attached PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
#8-32 threads, according to the hole pattern shown in the following figure. Use care to keep metal chips from falling into other equipment. Securely attach the rechargeable battery module to the panel mounting surface using four #8-32 x ½” flat head machine screws. #8-32 (four places) 6.435" 163.45 mm) 2.250" (57.15 mm) GFK-2741C March 2015...
If input power is turned off, the charger will reset. The charger starts a new charge cycle when the power is turned back on. 2.5.2.3 Indicators Mode Orange No battery / Initialization Fast charge Green/Orange Top-off charge Green Trickle charge (fully charged) Red/Green Error PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
5 years @ 20ºC 2.6.1.2 CPU Battery Low Indication The legacy batteries will not reliably provide the CPU with a battery low indication. User logic should not rely on any of the battery status bits when using these batteries. GFK-2741C March 2015...
If voltage is present, the fuse is not open. If no voltage is present, the internal fuse has probably opened and the unit will have to be replaced. Only perform this check in a non-hazardous environment. PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
(RX3i) or the slot in the bottom of the battery cover (RX7i) and close the compartment door (RX3i) or install the battery cover (RX7i). Be careful not to pinch the battery cable when closing the battery compartment cover. GFK-2741C March 2015...
Page 19
Notch at base of battery compartment Notch in Battery Cover An earlier version RX7i CPU may not have a slot in its battery door. For these CPUs, replace the door (supplied with the IC698ACC701 replacement battery). PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
Lithium Battery Warning Do not recharge, disassemble, heat or incinerate lithium batteries. Dispose of lithium batteries in accordance with federal, state, and local regulations. Be sure to consult with the appropriate regulatory agencies before disposing of batteries. GFK-2741C March 2015...
This product is a UL Recognized Component and has been evaluated to the following standard for use in ordinary location: UL 60601-1 (UL file E208921) Note: Charger has not been evaluated for use in hazardous areas and therefore should not be used in that environment. PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
Operating Temperature, surrounding air -25˚C to 60˚C Storage Temperature -40C to +85C (-40°F to 185°F) Humidity 5% to 95%, non-condensing Environment Restricted Access Area and Pollution Degree 2 environment as defined below. GFK-2741C March 2015...
Note: To remove the Energy Pack from the DIN rail, use a small flat-blade screwdriver to pull down on the tab on the bottom of the Energy Pack and then lift the module off the DIN rail. PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
Drill four mounting holes using the spacing shown in the following drawing. Use the machine screws and nuts to attach the Energy Pack to the panel. 2.610" 66.294mm 0.188" 4.763mm Drilling Pattern for Direct Panel Mounting GFK-2741C March 2015...
These terminals are reserved. Do not connect power to them. FGND 24 VDC 0 VDC Insert the plug into the Input Power connector of the Energy Pack and securely tighten the attaching screws. PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
Proper grounding of this device is essential. All ground wires must be as short as possible and terminate at the same grounding point. Panel Energy Pack Controller FGND FGND Central Earth Ground Point Ground Sample Grounding Connections GFK-2741C March 2015...
The Energy Pack supplies power long enough for the Controller to back up memory and then turns off power to the Controller. When the input voltage to the Energy Pack returns to normal, the power-up routine begins. PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
The firmware for the Energy Pack is automatically updated by the Controller. At power-up, the Controller checks the version of Energy Pack firmware to verify compatibility with the Controller firmware. If an update is needed, the Controller performs it automatically. LED Indications for Firmware Updates Firmware Update Mode All three LEDs blink green GFK-2741C March 2015...
PACSystems RX3i Energy Pack (IC695ACC400) Refer to PACSystems* RX3i Energy Pack IC695ACC400 IPI, GFK-2724. PACSystems RX3i Energy Pack (IC695ACC402) Refer to PACSystems* RX3i Energy Pack IC695ACC402 Quick Start Guide, GFK-2939. PACSystems* Controllers Battery and Energy Pack Manual GFK-2741C...
PACSystems* RX3i Energy Pack IC695ACC402 Quick Start Guide, GFK-2939 PACSystems RXi Distributed IO Controller User's Manual, GFK-2816 For user manuals, product updates and other information go to the Support website, http://www.ge-ip.com/support and refer to Controllers and IO. GFK-2741C March 2015...