3-3-2 Performing the operations of HWHP (CAHV) group
Text below explains how to perform HWHP (CAHV) operations.
3-3-2-1 Performing the operations that target one group
When you click on a group icon in the operation condition monitoring screen that shows the list of all groups,
the operation screen for that group will appear. The items shown in this screen are the current operation
conditions. Modify the items you want to change and click [OK] to confirm the operation details. Click
[Cancel] to return to the previous screen without making any changes.
Note: If the Web browser is configured to block Java Script, the operation window will appear at the left top of the floor layout
screen. If the floor layout window is scrolled down to click the group icon, scroll up the screen to the left to perform an
operation.
ON/OFF
Click to switch to ON or OFF.
Operation mode
Click to switch the operation
mode.
Set temperature
Click to adjust the set
temperature.
Cancel button
Click to cancel all operations.
Item
ON/OFF
Operation mode
Set temperature
Fan mode
3-3-2-2 Performing the operations that target all groups
Click [Batch Operation] from the operation condition monitoring screen, and the screen to set the batch
operation will appear.
After you have made settings on the screen for batch operation, click [OK] and the operation settings for only
the adjusted items will be sent to all the HWHP (CAHV) groups.
To return to the previous screen without performing any operations, click [Cancel].
Note: If operation of an item has been prohibited, then operation is not possible for that item.
Click [ON] or [OFF] to switch to ON or OFF.
Click [Heating], [Heating ECO], [Hot Water] or [Anti-freeze] to switch the operation mode.
Click
to adjust the set temperature.
Note: The temperature setting range is as follows:
Heating: 25-70ºC /77-158ºF
Heating ECO: Invalid
Hot Water: 25-70ºC /77-158ºF
Anti-freeze: Invalid (fixed at 25ºC/77ºF)
Click [Normal] or [Snow] to switch the fan mode.
Note: A function to prevent an accumulation of snow on top of the fan guard by forcing the fan to operate
even while the unit is stopped
Description
15
Group name
The name of the group is
displayed here.
Fan mode
Click to switch the fan mode.
OK button
Click to confirm the operation
details. You must press the OK
button for the operation to take
effect.