Mitsubishi Electric MXZ-8A140VA1 Technical & Service Manual

Mitsubishi Electric MXZ-8A140VA1 Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for MXZ-8A140VA1:

Advertisement

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
[Model name]
<Outdoor unit>
MXZ-8A140VA
<Branch box>
PAC-AK50BC
PAC-AK30BC
PAC-AK51BC
PAC-AK31BC
(Indispensable optional parts for MXZ-8A140VA)
OUTDOOR UNIT
BRANCH BOX
[Service Ref.]
MXZ-8A140VA
MXZ-8A140VA
MXZ-8A140VA
MXZ-8A140VA
PAC-AK50BC
CONTENTS
1. TECHNICAL CHANGES ................................... 2
2. SAFETY PRECAUTION .................................... 3
3. OVERVIEW OF UNITS ...................................... 6
4. SPECIFICATIONS ........................................... 14
5. DATA ................................................................ 16
6. OUTLINES AND DIMENSIONS ...................... 19
7. WIRING DIAGRAM ......................................... 21
9. TROUBLESHOOTING .................................... 27
10. ELECTRICAL WIRING .................................... 75
Model name
11. WIRING SPECIFICATIONS ............................. 76
indication
12. SYSTEM CONTROL ........................................ 77
13. REFRIGERANT PIPING TASK ....................... 79
14. DISASSEMBLY PROCEDURE ....................... 82
15. PARTS LIST .................................................... 88
16. RoHS PARTS LIST ......................................... 95
17. OPTIONAL PARTS .......................... Back cover
INDOOR UNITS COMBINATION SHEETS
April 2010
No. OC316
REVISED EDITION-E
HFC
utilized
R410A
Revision:
• PAC-AK51/31BC are added
in REVISED EDITION-E.
• Some descriptions have
been modified.
1
Please void OC316
REVISED EDITION-D.
2
NOTE:
3
• This service manual
describes technical data of
outdoor unit and branch box.
As for indoor units, refer to
its service manual.
• RoHS compliant products
have <G> mark on the
spec name plate.
• For servicing RoHS com-
pliant products, refer to the
RoHS PARTS LIST.

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric MXZ-8A140VA1

  • Page 1: Table Of Contents

    SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS April 2010 No. OC316 REVISED EDITION-E utilized TECHNICAL & SERVICE MANUAL R410A [Model name] [Service Ref.] Revision: <Outdoor unit> • PAC-AK51/31BC are added MXZ-8A140VA in REVISED EDITION-E. MXZ-8A140VA • Some descriptions have MXZ-8A140VA been modified. MXZ-8A140VA •...
  • Page 2: Technical Changes

    TECHNICAL CHANGES MXZ-8A140VA MXZ-8A140VA The parts below have been changed. • THERMISTOR (DISCHARGE/TH4) (Connector change) • CONTROLLER CIRCUIT BOARD (C.B) • NOISE FILTER CIRCUIT BOARD (N.F.) • ACTIVE FILTER MODULE (ACTM) • RELAY (52C), RESITOR (RS) (including N.F.) MXZ-8A140VA MXZ-8A140VA The parts below have been changed.
  • Page 3: Safety Precaution

    SAFETY PRECAUTION 2-1. ALWAYS OBSERVE FOR SAFETY Before obtaining access to terminal, all supply circuit must be disconnected. 2-2. CAUTIONS RELATED TO NEW REFRIGERANT Cautions for units utilizing refrigerant R410A Use new refrigerant pipes. Do not use refrigerant other than R410A. If other refrigerant (R22 etc.) is used, chlorine in refrige- Make sure that the inside and outside of refrige- rant can cause deterioration of refrigerant oil etc.
  • Page 4 [1] Cautions for service (1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.
  • Page 5 (2) Cautions for refrigerant piping work New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
  • Page 6: Overview Of Units

    OVERVIEW OF UNITS 3-1. CONSTRUCTION OF SYSTEM MXZ-8A140VA/ MXZ-8A140VA / MXZ-8A140VA / MXZ-8A140VA Rated capacity (kW) 14.0/16.0 (Cooling/Heating) Outdoor unit R410A Type 15 ~ Type 80 Indoor unit CAUTION : The indoor unit which rated capability exceeds Capacity 8.0kW (80 type) can NOT be connected. that can be connected Number of units...
  • Page 7 3-2. SYSTEM OUTLINE The additional connection of the Branch Box together with employment of the compact trunk-looking outdoor unit can successfully realizes a long distance piping for big houses. Equipped with a microcomputer, the Branch Box can trans- late the transmission signal of indoor units to achieve the optimum control. 3-2-1.
  • Page 8 3-3. TYPICAL COMBINATION EXAMPLE Branch box is located INSIDE of condominium Branch box (Inside) Installing branch box indoors Only 1 piping is required between the outdoor and indoor offering a fine external view. ■ System example of 5 indoor units Branch box (5 branch type) Master Dining...
  • Page 9 3-4. INSTALLATION 3-4-1. Outdoor unit installation location For best performance, select proper position. ● Avoid places where combustible gas may be generated or leak. ● Avoid direct sunlight or other sources of heat. ● Install sunshade to protect the outdoor unit if direct sunlight hits the unit. ●...
  • Page 10 (2) When installing a single outdoor unit Minimum dimensions are as follows, except for Max., meaning Maximum dimensions, indicated. Refer to the figures for each case. ● Obstacles at rear only (Fig. 2-4) ● Obstacles at rear and above only (Fig. 2-5) ·...
  • Page 11 (3) When installing multiple outdoor units Leave 10 mm space or more between the units. ● Obstacles at rear only (Fig. 2-10) ● Obstacles at rear and above only (Fig. 2-11) • No more than 3 units must be installed side by side. In addition, leave space as shown. •...
  • Page 12 3-4-3. Space required for Installation and servicing for Branch box. (1) Front View (Fig. 3-1) A Branch box B On the side of piping (2) Side View (Fig. 3-2, Fig. 3-3) C For indoor installations D Ceiling board E Maintenance hole F PCB side w1: A minimum 350 mm is required for 90°...
  • Page 13 3-5. SIMPLIFIED PIPING SYSTEM Piping connection size The piping connection size differs according to the type and capacity of indoor units. Liquid (mm) 9.52 Match the piping connection size of branch box with indoor unit. If the piping connection size of branch box does not match the piping connection size of indoor unit, use optional different-diameter (deformed) joints to the branch box side.
  • Page 14: Specifications

    SPECIFICATIONS • Outdoor unit : MXZ-8A140VA MXZ-8A140VA kcal/h = kW MXZ-8A140VA MXZ-8A140VA Conversion formula: Btu/h = kW 3412 /min 35.31 MXZ-8A140VA/ MXZ-8A140VA / MXZ-8A140VA / MXZ-8A140VA Service Ref. Rated Cooling capacity 14.0 Rated power consumption 3.79 Operating current 17.30/16.55/15.86, 17.30 Operating power factor 99.6 Starting current (Outdoor unit)
  • Page 15 • Branch box : PAC-AK50BC PAC-AK30BC PAC-AK51BC PAC-AK31BC PAC-AK50BC PAC-AK30BC Model name PAC-AK51BC PAC-AK31BC MAX. 5 MAX. 3 Connectable number of indoor units Single phase, 220/230/240V, 50Hz, Single phase, 220V, 60Hz Power supply (from outdoor unit) 0.003 Input Running current 0.05 Galvanized sheets External finish...
  • Page 16: Data

    DATA 5-1. CORRECTING COOLING AND HEATING CAPACITY 5-1-1. Correcting Changes in Air Conditions (1) The performance curve charts (Figure 1-1, 1-2, 2-1, 2-2) show the change ratio of capacity and input (power consumption) according to the indoor and outdoor temperature condition when define the rated capacity (total capacity) and rated input under the standard condition in standard piping length (5 m) as “1.0”.
  • Page 17 5-1-2. Correcting Capacity for Changes in the Length of Refrigerant Piping To obtain the ratio (and the corrected piping length) of the outdoor units rated capacity and the total in-use indoor capacity, first find the capacity ratio corresponding to the standard piping length from Fig. 3, Fig. 4 and then multiply by the capacity from Fig.1-1, 1-2, Fig.
  • Page 18 5-2. NOISE CRITERION CURVES MICROPHONE UNIT 1.5m GROUND MXZ-8A140VA SPL(dB) MODE LINE COOLING MXZ-8A140VA HEATING MXZ-8A140VA MXZ-8A140VA NC-70 NC-60 NC-50 NC-40 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR NC-20 CONTINUOUS NOISE 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz...
  • Page 19: Outlines And Dimensions

    OUTLINES AND DIMENSIONS 6-1. OUTDOOR UNIT unit : mm MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA 2 SERVICE SPACE 3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS 1 FREE SPACE (Around the unit) The diagram below shows a basic Dimensions of space needed Please secure the unit firmly Piping and wiring connections for service access are with 4 foundation (M10) bolts.
  • Page 20 6-2. BRANCH BOX UNIT unit : mm PAC-AK50BC PAC-AK51BC SUSPENSION BOLT PITCH SUSPENSION BOLT : W3/8 (M10) REFRIGERANT PIPE FLARED CONNECTION (inch) TO OUTDOOR UNIT LIQUID PIPE GAS PIPE DRAIN HOSE SIZE : O.D. 20 (VP-16) 3-ELECTRIC WIRE INLET TERMINAL BLOCK TO INDOOR UNIT TO INDOOR UNIT 3-WIRE BAND...
  • Page 21: Wiring Diagram

    WIRING DIAGRAM 7-1. OUTDOOR UNIT MXZ-8A140VA...
  • Page 22 MXZ-8A140VA MXZ-8A140VA...
  • Page 23 MXZ-8A140VA...
  • Page 24 7-2. BRANCH BOX : PAC-AK50BC PAC-AK30BC PAC-AK51BC PAC-AK31BC Note : " PAC - AK30 . 50BC, PAC - AK31 . 51BC " is only for R410A. SYMBOL NAME Branch box controller board <B.C> Fuse 250V 6.3A SW1<B.C> Switch for service CNM<B.C>...
  • Page 25: Necessary Conditions For System Construction

    NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION REFRIGERANT SYSTEM DIAGRAM MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA High pressure sensor Condenser / evaporator discharge pressure sensor Room temperature temperature thermistor Check valve 63HS (TH5 or RT12) thermistor (TH1 or RT11) Bypass valve(SV2) (High Pressure) 4-way valve Thermistor TH7 Bypass valve (SV1) (Outdoor temperature)
  • Page 26 ■ Pipe size (Branch box-Indoor unit) *Case of M series or S series Indoor unit Indoor unit (kW) type Liquid 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 9.52 9.52 Pipe size (mm) 9.52 9.52 9.52 9.52 9.52 9.52 12.7 15.88 15.88 15.88...
  • Page 27: Troubleshooting

    TROUBLESHOOTING 9-1. TROUBLESHOOTING <Error code display by self-diagnosis and actions to be taken for service (summary)> Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the table below.
  • Page 28 9-2. CHECK POINTS FOR TEST RUN 9-2-1. Before test run ● Turn on the main power switch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely damage the internal parts. Keep the main power switch turned on during the operation season. ●...
  • Page 29 (2) Using SW4 in outdoor unit In case of the test run from outdoor unit, all indoor units operate. Therefore, you cannot detect any erroneous con- nection of refrigerant pipes and the connecting wires. If it aims at detection of any erroneous connection, be sure to carry out the test run from remote controller with reference to "(1) Using remote controller."...
  • Page 30 9-3. SELF-DIAGNOSIS ACTION TABLE <Abnormalities detected when the power is put on> (Note 1) Refer to indoor unit section for code P and code E. Abnormal point and detection method Judgment and action Error Code Case 1 No voltage is supplied to termi- 1 Check following items.
  • Page 31 Error Code Abnormal point and detection method Case Judgment and action 1 Check disconnection or looseness or polar- Indoor–branch box/branch box–outdoor 1 Contact failure or miswiring of unit connector miswiring, excessive ity of indoor –branch box/branch box–outdoor indoor/outdoor unit connecting unit connecting wire of indoor and outdoor number of units wire...
  • Page 32 <Abnormalities detected while unit is operating> Abnormal point and detection method Judgment and action Error Code Case (1) High-pressure switch (63H) operated 1) Short cycle of indoor unit 1)~6) Check indoor unit and repair defect. 2) Clogged filter of indoor unit Abnormal if high-pressure switch 63H oper- ated ( w ) during compressor operation.
  • Page 33 Error Code Abnormal point and detection method Case Judgment and action (1) High discharging temperature 1 Overheated compressor opera- 1 Check intake superheat. Abnormal if discharge temperature ther- tion caused by shortage of Check leakage of refrigerant. mistor (TH4) exceeds 125: or 110: refrigerant Charge additional refrigerant.
  • Page 34 Abnormal point and detection method Judgment and action Error Code Case 1 Check the connector’s contact and the electric (1) Open/short circuit in the outdoor unit 1One or more connectors on wires of thermistor. outdoor controller circuit board thermistors (TH3, TH7, and TH8) and (TH3, TH7 and TH8) and branch branch box’s thermistors (TH-A~E) box controller board (TH-A~E)
  • Page 35 Abnormal point and detection method Judgment and action Error Code Case (1) Too low superheat due to low dis- 1 Disconnection or loose 12 Check the installation conditions of charge temperature connection of discharge discharge temperature thermistor (TH4). Abnormal if discharge superheat is contin- temperature thermistor.
  • Page 36 Abnormal point and detection method Judgment and action Error Code Case Current sensor error 1 Disconnection of compressor 1 Correct the wiring (U·V·W phase) to com- Abnormal if current sensor detects –1.5A wiring pressor. Refer to 9-7. to 1.5A during compressor operation. (This 2 Defective circuit of current 2 Replace outdoor power circuit board.
  • Page 37 Abnormal point and detection method Judgment and action Error Code Case Indoor - branch box/branch box - 1 Indoor–branch box/ 1 Check disconnection or looseness of indoor– branch box–outdoor unit con- outdoor unit communication error branch box/branch box–outdoor unit connect- necting wire has contact failure.
  • Page 38 9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA Phenomena Factor Countermeasure 1. Remote controller display operates 1 Refrigerant shortage 1 If refrigerant leaks, discharging tempera- normally and the unit performs cool- ture rises and LEV opening increases. ing operation, however, the capacity Inspect leakage by checking the tem- cannot be fully obtained.
  • Page 39 9-5. SPECIAL FUNCTIONS 9-5-1. Low noise mode (on-site modification) (Fig. 9-1) By performing the following modification, operation noise of the outdoor unit can be reduced by about 3-4 dB. The low noise mode will be activated when a commercially available timer or the contact input of an ON/OFF switch is added to the CNDM connector (optional parts) on the control board of the outdoor unit.
  • Page 40 9-6. HOW TO CHECK THE PARTS OUTDOOR UNIT : MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA Parts name Check points Disconnect the connector then measure the resistance with a tester. Thermistor (TH3) (At the ambient temperature 10 ~30 ) <Outdoor pipe> Normal Abnormal Thermistor (TH4) <Discharge>...
  • Page 41 Check method of DC fan motor (fan motor / outdoor controller circuit board) Notes · High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service. · Do not pull out the connector (CNF1, 2) for the motor with the power supply on. (It causes trouble of the outdoor controller circuit board and fan motor.) Self check...
  • Page 42 <Thermistor feature chart> Low temperature thermistors Pipe temperature thermistor <Liquid> (TH3) Pipe temperature thermistor <Cond.> (TH6) Outdoor temperature thermistor (TH7) Gas pipe temperature thermistor (TH-A ~ TH-E)···· Branch box Thermistor R0 = 15k' ± 3% B constant = 3480 ± 2% =15exp{3480( 273+t –...
  • Page 43: Pac-Ak51Bc

    BRANCH BOX : PAC-AK50BC PAC-AK30BC PAC-AK51BC PAC-AK31BC Parts name Check points Disconnect the connector then measure the resistance with a tester. Thermistor (TH-A~E) (At the ambient temperature 10 ~30 ) <Gas pipe> Normal Abnormal 4.3k ~ 9.6k Open or short Disconnect the connector then measure the resistance with a tester.
  • Page 44 Linear expansion valve (LEV) in Branch box (1) Operation summary of the linear expansion valve • Linear expansion valve open/close through stepping motor after receiving the pulse signal from the branch box controller board. • Valve position can be changed in proportion to the number of pulse signal. <Connection between the branch box controller board and the linear expansion valve>...
  • Page 45 (3) How to attach and detach the coil of linear expansion valve <Composition> Linear expansion valve is separable into the main body and the coil as shown in the diagram below. Main body Coil Lead wire Stopper <How to detach the coil> Hold the lower part of the main body (shown as A) firmly so that the main body does not move and detach the coil by pulling it upward.
  • Page 46 Troubleshooting Check point Corrective measure Problem Locked expansion Replace the linear If the linear expansion valve becomes locked and the motor is still operating, valve expansion valve. the motor will emit a clicking noise and will not function. This clicking noise indicates an abnormality.
  • Page 47 9-7. TEST POINT DIAGRAM <CAUTION> TEST POINT1 is high voltage. 9-7-1. Outdoor controller circuit board MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA (TEST POINT 2) (voltage between pins of C6B): DC 15V (TEST POINT 1) (voltage between pins of (Branch box/outdoor unit connecting wire) C5E): DC280V-350V Communication High pressure switch...
  • Page 48 <CAUTION> TEST POINT1 is high voltage. Outdoor controller circuit board MXZ-8A140VA Forced defrost, CN3S detect history record reset CN51 CNDM Model select 1 to 2: Input of low noise Test operation mode 1 to 3: Input of external con- tact point Function switch CN52C (Connect to the noise...
  • Page 49 9-7-2. Outdoor noise filter circuit board MXZ-8A140VA LO, NO Voltage of 220-240V AC is output (Connect to the outdoor power circuit board (SC-R, SC-S)) CNAC1, CNAC2 220-240V AC (Connect to the outdoor control- ler circuit board (CNAC)) Primary current (Connect to the outdoor power circuit board (CN5))
  • Page 50 Outdoor noise filter circuit board MXZ-8A140VA MXZ-8A140VA LO, NO Voltage of 220-240V AC is output TABS (Connect to the outdoor power circuit board) TABT CNAC1, CNAC2 220-240V AC (Connect to the outdoor control- ler circuit board (CNAC)) Primary current (Connect to the outdoor power circuit board (CN5))
  • Page 51 Outdoor noise filter circuit board MXZ-8A140VA CN52C 52C driving signal (Connect to the outdoor controller circuit board (CN52C).) LO, NO Voltage of 220-240V AC is output (Connect to the outdoor CNAC1, CNAC2 power circuit board 220-240V AC (TABS, TABT)) (Connect to the outdoor control- ler circuit board (CNAC))
  • Page 52 Brief Check of POWER MODULE 9-7-3. Outdoor power circuit board W Usually, they are in a state of being short-circuited if they are broken. Measure the resistance in the following points (connectors, etc.). MXZ-8A140VA If they are short-circuited, it means that they are broken. 1.
  • Page 53 Brief Check of POWER MODULE Outdoor power circuit board W Usually, they are in a state of being short-circuited if they are broken. Measure the resistance in the following points (connectors, etc.). MXZ-8A140VA If they are short-circuited, it means that they are broken. MXZ-8A140VA 1.
  • Page 54 9-7-4. Branch box controller board PAC-AK50BC PAC-AK30BC PAC-AK51BC PAC-AK31BC LED1 Transmission start-up state display TH-A to E Connect to LEV-A to E Start-up : LED1 blinks Thermistor-A to E (0.5sec. : ON, 0.5sec. : OFF) Connect to LEV-A to E TH-A to C for PAC-AK30/31BC LEV-A to C for PAC-AK30/31BC Start-up completion: LED1 lights...
  • Page 55 9-7-5. Active filter module MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA Connect to the outdoor L1, L2 power circuit board (TABP1) Connect to the DCL (Reactor) – Connect to the outdoor power circuit board (TABN1) Connect to the outdoor power circuit board (CNAF) : GND 2-1 : 15V DC 3-1 : Control signal 4, 5 : Not used...
  • Page 56 Active filter module MXZ-8A140VA Connect to the outdoor power circuit board (TABP2) L1, L2 Connect to the DCL (Reactor) Non-connect Lower side Upper side Non-connect Connect to the outdoor power circuit board (TABP1) – Connect to the outdoor power Connect to the outdoor power Connect to the outdoor power circuit board (TABN2) circuit board (TABN1)
  • Page 57 9-8. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS (1) Function of switches Action by the switch operation Type of Switch Function Effective timing Switch When compressor is Forced defrost Start Normal operating in heating operation. Clear Normal Abnormal history clear off or operating No function —...
  • Page 58 MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA Action by the switch operation Type of Switch Function Effective timing Switch — — — No function Switching the target Target sub-cool down Normal Always sub-cool (Heating mode) — — — No function — — — No function Capability cut Demand switching Normal...
  • Page 59 MXZ-8A140VA Type of Action by the switch operation Switch Function Effective timing Switch No function — — — Switching the target Target sub-cool down Normal Always sub-cool (Heating mode) — — — 3, 4 No function — — — 5, 6 No function Capability cut Demand switching...
  • Page 60 <Outdoor unit operation monitor function> Digital indicator LED3 displays 2 digit number or code to inform operation condition and the meaning of error code by controlling DIP SW2 on outdoor controller. Operation indicator SW2 : Indicator change of self diagnosis SW2 setting Display detail Explanation for display...
  • Page 61 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Pipe temperature / Liquid (TH3) – 40~90 – 40~90 (When the coil thermistor detects 0: or below, “–” and temperature are displayed by turns.) (Example) 2 3 4 5 6 When –10:;...
  • Page 62 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Pipe temperature / Liquid (TH3) on error – 40~90 occurring (When the coil thermistor detects 0: or below, “–” – 40~90 and temperature are displayed by turns.) (Example) When –15:;...
  • Page 63 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Capacity setting display Displayed as an outdoor capacity code. Code Capacity Code display MXZ-8A140VA 2 3 4 5 6 Outdoor unit setting information •...
  • Page 64 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Indoor setting temperature 17~30 17~30 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 2 3 4 5 6 Indoor unit 5 Indoor unit 6 Indoor unit 7...
  • Page 65 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Target Sub-cool (Cooling mode) : SCm 0~255 2 3 4 5 6 Error postponement code history (2) Postponement code display of outdoor unit Blinking: During postponement Code Lighting: Cancellation of postponement...
  • Page 66 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Indoor pipe temperature / Liquid on – 39~88 error occurring (When the temperature is 0 °C or less, “–” and – 39~88 temperature are displayed by turns.) Indoor unit 1 (Example)
  • Page 67 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Thermostat-on time until error stops 0~999 0~999 (When it is 100 minutes or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 415 minutes;...
  • Page 68 <Branch box unit operation monitor function> [When option part ‘A-Control Service Tool (PAC-SK52ST)’ is connected to branch box controller board (CNM)] Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of error code by controlling DIP SW2 on ‘A-Control Service Tool’.
  • Page 69 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit LEV-B opening pulse 0~500 0~500 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns. Pulse (Example) 2 3 4 5 6...
  • Page 70 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Indoor pipe temperature / Liquid – 35~88 (When the temperature is 0: or less, “–” and Indoor-B temperature are displayed by turns.) –...
  • Page 71 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Outdoor heatsink temperature (TH8) – 40~200 – 40~200 (When the temperature is 0: or less, “–” and temperature are displayed by turns.) (When the thermistor detects 100: or more, hundreds digit, tens digit and ones digit are 2 3 4 5 6...
  • Page 72 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Branch pipe temperature – 39~88 TH-A 2 3 4 5 6 Branch pipe temperature – 39~88 TH-B 2 3 4 5 6 Branch pipe temperature –...
  • Page 73 ■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Indoor - setting temperature 16~31 16~31 Indoor-A 2 3 4 5 6 Indoor - setting temperature 16~31 16~31 Indoor-B 2 3 4 5 6 Indoor - setting temperature 16~31 16~31...
  • Page 74 9-9. SELECTING FUNCTIONS USING THE REMOTE CONTROLLER Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1. (1) Functions available when setting the unit number to 00 W1 The functions table below are available only when P-series indoor unit and the wired remote controller is used.
  • Page 75: Electrical Wiring

    ELECTRICAL WIRING External wiring procedure (Fig.1) E Power supply: Single phase 220/230/240V, 50Hz 220V, 60Hz, Max. Permissive system Impedance : 0.22(") Note: 1 Power supply input: Outdoor unit only. Connect the lines (C), (D) in accordance with the terminal block names to ensure correct polarity.
  • Page 76: Wiring Specifications

    WIRING SPECIFICATIONS Warning: In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing.
  • Page 77: System Control

    SYSTEM CONTROL 12-1. BASIC SYSTEMS NOTE: The indoor units can be OC : Outdoor unit connected to any of the BC : Branch box 5 connectors IC : Indoor unit (5- branch type) or 3 connectors RC : Remote controller (3- branch type) of the branch box.
  • Page 78 12-3. INCORRECT SYSTEMS 12-3-1. Group operation by single remote controller BC (3- branch type) • Plural indoor units cannot be operated by a single remote controller. 12-3-2. Group operation between different refrigerant systems BC (3- branch type) BC (3- branch type) •...
  • Page 79: Refrigerant Piping Task

    REFRIGERANT PIPING TASK 13-1. ADDITIONAL REFRIGERANT CHARGE a7 a8 Outdoor unit Branch box Indoor unit Total piping length b1 + b2 + a1+ a2 + a3 + a4 + a5 + a6 + a7 + a8 115m Farthest piping length (L) b2 + a8 70m (b2 55m, a8...
  • Page 80 <Table 1> Total piping length 40m or less 41 – 50m 51 – 70m 71 – 90m 91 – 115m (b1+ b2 + a1+ a2 + a3 + a4 + a5 + a6 + a7 + a8) Additional refrigerant charging amount 0kg (no need) 0.6kg 1.4kg...
  • Page 81 13-2. PRECAUTIONS AGAINST REFRIGERANT LEAKAGE 13-2-1. Introduction (2) Calculate room volumes (m³) and find the room with the smallest volume R410A refrigerant of this air conditioner is non-toxic and non-flammable but leaking of large amount from an indoor The part with represents the room with the smallest unit into the room where the unit is installed may be deleteri- volume.
  • Page 82: Disassembly Procedure

    DISASSEMBLY PROCEDURE OUTDOOR UNIT : MXZ-8A140VA/ MXZ-8A140VA / MXZ-8A140VA / MXZ-8A140VA OPERATING PROCEDURE PHOTOS & ILLUSTRATION 1. Removing the service panel and top panel Top panel fixing screws Top panel Figure 1 (1) Remove 3 service panel fixing screws (5 × 10) and slide the hook on the right downward to remove the service Service panel panel.
  • Page 83 OPERATING PROCEDURE PHOTOS 4. Removing the thermistor <Outdoor 2-phase pipe> (TH6) Photo 4 Thermistor (1) Remove the service panel. (See Figure 1.) <Outdoor 2-phase pipe> (TH6) (2) Remove the top panel. (See Figure 1.) Controller circuit board (C.B.) (3) Disconnect the connectors, TH6 and TH7 (red), on the con- troller circuit board in the electrical parts box.
  • Page 84 OPERATING PROCEDURE PHOTOS 7. Removing the solenoid valve coil <4-way valve> (21S4) Photo 7 (1) Remove the service panel. (See Figure 1.) (2) Remove the top panel. (See Figure 1.) [Removing the solenoid valve coil <4-way valve>] Solenoid valve coil 4-way valve (3) Remove 4-way valve solenoid coil fixing screw <4-way valve>...
  • Page 85 OPERATING PROCEDURE PHOTOS Photo 9 11. Removing the high pressure switch (63H) and low pres- sure switch (63L) (1) Remove the service panel. (See Figure 1.) High pressure switch (63H) Low pressure switch (63L) (2) Remove the top panel. (See Figure 1.) (3) Remove the electrical parts box.
  • Page 86 BRANCH BOX : PAC-AK50BC PAC-AK30BC PAC-AK51BC PAC-AK31BC OPERATING PROCEDURE PHOTOS 1. Removing the controller cover and under panel Photo 1 (1) Remove 3 controller cover fixing screws (4 o 10) to detach Under panel fixing screws the cover. (See Photo 1.) (2) Remove 6 under panel fixing screws (4 o 10) to remove the panel.
  • Page 87 OPERATING PROCEDURE PHOTOS 4. Removing the LEV coil (LEV-A–E) Photo 4 (1) Remove the controller cover. (See Photo 1.) (2) Remove the under cover. (See Photo 1.) Separator fixing screws (3) Remove 4 separator fixing screws (4 o 10) in the side of the branch box.
  • Page 88: Parts List

    PARTS LIST (non-RoHS compliant) 15-1. FUNCTIONAL AND ELECTRICAL PARTS MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA Q'ty/set Recom- Wiring MXZ-8A140 Part No. mended Specification Remarks Diagram Part Name Symbol Q'ty MF1, MF2 FAN MOTOR MF1, MF2 FAN MOTOR PROPELLER SOLENOID VALVE COIL...
  • Page 89 Part numbers that are circled are not shown in the figure. Q'ty/set Wiring Recom- Remarks Diagram mended MXZ-8A140 Part No. Part Name Specification Symbol Q'ty SOLENOID VALVE (SV1) 63HS HIGH PRESSURE SENSOR CHARGE PLUG ANB33FDCMT COMPRESSOR STOP VALVE BALL VALVE STRAINER ACCUMULATOR OIL SEPARATOR...
  • Page 90 15-2. FUNCTIONAL PARTS BRANCH BOX : PAC-AK50BC...
  • Page 91 Part numbers that are circled are not shown in the figure. Q'ty/set Wiring Recom- Remarks Diagram mended Part No. Part Name Specification PAC-AK50BC Symbol Q'ty TOP PANEL COVER-L COVER-G SIDE PANEL LEV COIL LEV-A–E SEPARATOR – (RG02N539G06) DRAIN PAN UNDER PANEL CONTROLLER COVER DRAIN HOSE CONTROLLER BOARD...
  • Page 92 15-3. FUNCTIONAL PARTS BRANCH BOX : PAC-AK30BC...
  • Page 93 Part numbers that are circled are not shown in the figure. Wiring Recom- Q'ty/set Remarks Part No. Part Name Specification Diagram mended PAC-AK30BC Symbol Q'ty TOP PANEL COVER-L COVER-G SIDE PANEL LEV COIL LEV-A–C – SEPARATOR (RG02N539G06) DRAIN PAN UNDER PANEL CONTROLLER COVER DRAIN HOSE CONTROLLER BOARD...
  • Page 94 15-4. STRUCTURAL PARTS MXZ-8A140VA MXZ-8A140VA MXZ-8A140VA 15 14 5 6 7 8 Q , ty/set Wiring Recom- Remarks Specification MXZ-8A140 Diagram mended Part No. Part Name (Drawing No.) Symbol VA,VA – F.ST SCREW (5×10) (DG12F536H10) SIDE PANEL (L) FAN GRILLE FRONT PANEL –...
  • Page 95: Rohs Parts List

    RoHS PARTS LIST 16-1. STRUCTURAL PARTS MXZ-8A140VA MXZ-8A140VA 15 14 5 6 7 8 Q'ty/set Wiring Recom- Remarks Specification Part No. Part Name Diagram mended (Drawing No.) MXZ-8A140VA Symbol Q'ty F.ST SCREW – (DG12F536H10) (5×10) SIDE PANEL (L) T7W E03 662 FAN GRILLE T7W E03 691 FRONT PANEL...
  • Page 96 16-2. FUNCTIONAL AND ELECTRICAL PARTS MXZ-8A140VA MXZ-8A140VA Q'ty/set Wiring Recom- Part No. Diagram mended Specification Remarks Part Name MXZ-8A140 Q'ty Symbol MF1, MF2 FAN MOTOR MF1, MF2 FAN MOTOR PROPELLER FAN SOLENOID VALVE COIL SOLENOID VALVE COIL...
  • Page 97 Part numbers that are circled are not shown in the figure. Q'ty/set Wiring Recom- Part Name Specification Remarks Part No. mended MXZ-8A140 Diagram Symbol Q'ty R01 E15 428 SOLENOID VALVE (SV1) HIGH PRESSURE SENSOR R01 E07 208 63HS CHARGE PLUG R01 E14 413 T97 415 779 COMPRESSOR...
  • Page 98 16-3. FUNCTIONAL PARTS BRANCH BOX : PAC-AK50BC PAC-AK51BC...
  • Page 99 Part numbers that are circled are not shown in the figure. Q'ty/set Wiring Recom- PAC-AK Remarks Part No. Part Name Specification Diagram mended Symbol Q'ty 50BC 51BC TOP PANEL COVER-L COVER-G SIDE PANEL LEV COIL LEV-A–E – SEPARATOR (BH00G766G04) DRAIN PAN UNDER PANEL T7W E02 669 UNDER PANEL...
  • Page 100 16-4. FUNCTIONAL PARTS BRANCH BOX : PAC-AK30BC PAC-AK31BC...
  • Page 101 Part numbers that are circled are not shown in the figure. Q'ty/set Wiring Recom- PAC-AK Remarks Diagram mended Part No. Part Name Specification Symbol Q'ty 30BC 31BC TOP PANEL COVER-L COVER-G SIDE PANEL LEV COIL LEV-A–C – SEPARATOR (BH00G766G04) DRAIN PAN UNDER PANEL T7W E02 669 UNDER PANEL...
  • Page 102: Optional Parts

    Special optional cover for outdoor installation of branch box HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN cCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Apr. 2010 No.OC316 REVISED EDITION-E PDF 5 Distributed in Aug. 2007 No.OC316 REVISED EDITION-D PDF 8 Distributed in Aug.
  • Page 103 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V - 1500 - 1500 - 2000 - 2000 - 2200 - 2200 1050 - 2500 -...
  • Page 104 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2000 2000 5000 9000 2830 13.0 12.4 11.9 2000 2000 6000 10000 3090 14.2 13.6 13.0 2000 2000...
  • Page 105 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 3200 5400 5400 14000 3660 16.8 16.1 15.4 4670 4670 4670 14000 5240 24.1 23.0 22.1 4380 4380...
  • Page 106 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1400 2330 4670 5600 14000 5240 24.1 23.0 22.1 1300 2170 4350 6170 14000 4600 21.1 20.2 19.4...
  • Page 107 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2200 2200 2500 6000 12900 4600 21.1 20.2 19.4 2200 2200 2500 7100 14000 5220 24.0 22.9 22.0...
  • Page 108 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2970 2970 2970 5090 14000 4400 20.2 19.3 18.5 2780 2780 2780 5650 14000 3940 18.1 17.3 16.6...
  • Page 109 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1500 1500 2200 2500 3500 11200 3660 16.8 16.1 15.4 1500 1500 2200 2500 4200 11900 4030 18.5...
  • Page 110 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1500 2000 2200 3500 3500 12700 4480 20.6 19.7 18.9 1500 2000 2200 3500 4200 13400 4910 22.5...
  • Page 111 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1290 1880 3610 3610 3610 14000 4500 20.7 19.8 18.9 1230 1800 3440 3440 4090 14000 4140 19.0...
  • Page 112 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1530 1530 1680 3830 5430 14000 3690 16.9 16.2 15.5 1540 1540 1680 4620 4620 14000 3730 17.1...
  • Page 113 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1640 2060 2060 4120 4120 14000 4180 19.2 18.4 17.6 1560 1940 1940 3890 4670 14000 3790 17.4...
  • Page 114 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2500 2500 2500 2500 2500 12500 4360 20.0 19.1 18.4 2500 2500 2500 2500 3500 13500 4970 22.8...
  • Page 115 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1270 1270 1270 1700 4240 4240 14000 4400 20.2 19.3 18.5 1200 1200 1200 1600 4000 4800 14000...
  • Page 116 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1350 1350 1790 1970 3770 3770 14000 4870 22.4 21.4 20.5 1280 1280 1710 1880 3590 4260 14000...
  • Page 117 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1500 2000 2000 2000 2000 3500 13000 4660 21.4 20.5 19.6 1500 2000 2000 2000 2000 4200 13700...
  • Page 118 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1210 1610 1770 2010 3380 4020 14000 4010 18.4 17.6 16.9 1140 1520 1670 1900 3200 4570 14000...
  • Page 119 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2000 2000 2000 2000 2000 3500 13500 4970 22.8 21.8 20.9 1970 1970 1970 1970 1970 4140 14000...
  • Page 120 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1600 1600 2000 2000 2000 4800 14000 3980 18.3 17.5 16.8 1750 1750 2190 2190 3060 3060 14000...
  • Page 121 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1690 1920 1920 1920 1920 4620 14000 3730 17.1 16.4 15.7 1840 2100 2100 2100 2930 2930 14000...
  • Page 122 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1500 1500 1500 1500 2200 2200 3500 13900 5230 24.0 23.0 22.0 1440 1440 1440 1440 2110 2110...
  • Page 123 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1150 1150 1150 1690 1690 1690 5460 14000 3730 17.1 16.4 15.7 1500 1500 1500 2200 2200 2500...
  • Page 124 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1170 1170 1560 1720 1720 2740 3910 14000 3830 17.6 16.8 16.1 1180 1180 1570 1730 1730 3300...
  • Page 125 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1240 1650 1650 1650 2050 2880 2880 14000 4180 19.2 18.4 17.6 1190 1580 1580 1580 1980 2770...
  • Page 126 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1900 1900 1900 1900 1900 2100 2380 14000 5220 24.0 22.9 22.0 1780 1780 1780 1780 1780 1960...
  • Page 127 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1960 1960 1960 1960 1960 1960 2230 14000 4810 22.1 21.1 20.2 1840 1840 1840 1840 1840 1840...
  • Page 128 MXZ-8A140VA COOLING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1730 1730 1730 1730 1730 1730 1730 1890 14000 4550 20.9 20.0 19.1 1700 1700 1700 1700 1700...
  • Page 129 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1700 1700 2200 2200 3300 3300 1130 3600 3600 1240 4000 4000 1370 5500 5500 1890 7200 7200...
  • Page 130 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1710 3990 3990 9700 3450 15.8 15.2 14.5 1710 3990 4790 10500 3770 17.3 16.6 15.9 1710 3990...
  • Page 131 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2860 4010 5730 12600 4510 20.7 19.8 19.0 2850 4000 6850 13700 4850 22.3 21.3 20.4 2860 4010...
  • Page 132 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1720 1720 5730 5730 14900 5230 24.0 23.0 22.0 1710 1710 5710 6860 16000 5540 25.4 24.3 23.3...
  • Page 133 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1450 4850 4850 4850 16000 4390 20.2 19.3 18.5 1370 4570 4570 5490 16000 4050 18.6 17.8 17.0...
  • Page 134 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2130 2130 4850 6880 16000 4390 20.2 19.3 18.5 2150 2150 5850 5850 16000 4430 20.3 19.5 18.6...
  • Page 135 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2630 3680 4420 5260 16000 4920 22.6 21.6 20.7 2470 3460 4150 5920 16000 4500 20.7 19.8 18.9...
  • Page 136 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1720 1720 2290 2520 6850 15100 5290 24.3 23.2 22.3 1680 1680 2240 2460 7940 16000 5370 24.7...
  • Page 137 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1320 1320 3690 4400 5270 16000 3850 17.7 16.9 16.2 1330 1330 4440 4440 4440 16000 3900 17.9...
  • Page 138 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1360 1820 3180 3180 6450 16000 4020 18.5 17.7 16.9 1560 2080 3640 4360 4360 16000 4830 22.2...
  • Page 139 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1440 2400 2400 4020 5740 16000 4320 19.8 19.0 18.2 1350 2250 2250 3780 6370 16000 3960 18.2...
  • Page 140 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1980 1980 2160 4940 4940 16000 4500 20.7 19.8 18.9 1860 1860 2050 4650 5580 16000 4150 19.1...
  • Page 141 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1890 2080 3310 3980 4730 16000 4250 19.5 18.7 17.9 1790 1970 3130 3750 5360 16000 3930 18.0...
  • Page 142 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2110 2400 3350 3350 4790 16000 4320 19.8 19.0 18.2 1990 2260 3160 3160 5420 16000 3990 18.3...
  • Page 143 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1720 1720 1720 1720 2290 5730 14900 5230 24.0 23.0 22.0 1710 1710 1710 1710 2280 6860 16000...
  • Page 144 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1350 1350 1350 1990 4520 5420 16000 3990 18.3 17.5 16.8 1710 1710 1710 2850 2850 2850 13700...
  • Page 145 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1710 1710 2280 2850 2850 3990 15400 5380 24.7 23.6 22.6 1690 1690 2250 2820 2820 4730 16000...
  • Page 146 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1370 1370 2280 3200 3200 4570 16000 4050 18.6 17.8 17.0 1300 1300 2160 3030 3030 5180 16000...
  • Page 147 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1710 2280 2510 2510 2510 3980 15500 5410 24.8 23.8 22.8 1680 2240 2460 2460 2460 4700 16000...
  • Page 148 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1330 1950 1950 2220 2220 6310 16000 3900 17.9 17.1 16.4 1560 2280 2280 2600 3640 3640 16000...
  • Page 149 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2150 2150 2150 2360 2680 4510 16000 5060 23.2 22.2 21.3 2040 2040 2040 2240 2550 5090 16000...
  • Page 150 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2020 2230 2230 2230 2230 5060 16000 4660 21.4 20.5 19.6 1900 2090 2090 2090 2090 5710 16000...
  • Page 151 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 2390 2720 2720 2720 2720 2720 16000 5160 23.7 22.7 21.7 2240 2550 2550 2550 2550 3560 16000...
  • Page 152 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1710 1710 1710 1710 2280 2510 2850 14500 5100 23.4 22.4 21.5 1720 1720 1720 1720 2290 2520...
  • Page 153 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1300 1300 1300 1730 1730 4320 4320 16000 3760 17.3 16.5 15.8 1720 1720 1720 2280 2520 2520...
  • Page 154 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1320 1320 1770 1770 1770 1770 6280 16000 3870 17.8 17.0 16.3 1710 1710 2280 2280 2280 2510...
  • Page 155 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1570 1570 2300 2300 2300 2300 3660 16000 4880 22.4 21.4 20.5 1500 1500 2200 2200 2200 2200...
  • Page 156 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1640 2190 2190 2410 2410 2410 2740 16000 5210 23.9 22.9 21.9 1540 2050 2050 2260 2260 2260...
  • Page 157 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1320 1920 2200 2200 2200 3080 3080 16000 3850 17.7 16.9 16.2 1450 2420 2420 2420 2420 2420...
  • Page 158 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1860 1860 2050 2320 2320 2320 3250 16000 4150 19.1 18.2 17.5 1790 1790 1970 2230 2230 2230...
  • Page 159 MXZ-8A140VA HEATING Total Outdoor Operated indoor unit Each capacity of unit (W) Outdoor unit current (A) rated Unit Power capacity input factor 220V 230V 240V 1370 1370 1370 1370 1370 1370 3200 4570 16000 4050 22.6 21.6 20.7 1300 1300 1300 1300 1300...
  • Page 160 Related Links Model Number: MXZ8A140VA-3 MXZ-8A_Parts_Catalog_(OC316E) MXZ-8A_Service_Manual_(OC316E)