Introduction
The Mechanical Counter, shown in Figure
800-4000
installed in
ampere frame Power Break® II
circuit breakers. Its function is to count the number of
times the breaker is closed. The catalog number when
ordered with a circuit breaker for factory installation is
SPCOUNTER.
The
catalog
installable Mechanical Counter kit is SPCOUNTERR.
Figure
1.
Mechanical Counter.
Operation
The count displayed by the Mechanical Counter is
incremented each time the circuit breaker is closed.
Installation
WARNING:
Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources, and
discharge the closing springs.
AVERTISSEMENT:
Avant
mettre le disjoncteur en position OFF, le deconnecter
de
toute
tension
d'alimentation,
ressorts d'armement
Install
the
Mechanical
procedure.
1.
Turn off the breaker, discharge the springs, and
turn off control power to the accessories
motor operator (if present). If it is a draw-out
breaker, rack it out.
2.
#8-32
Loosen the four
assembly and remove the trim plate.
1,
can be
number
of
the
d'installer
tout
accessoire,
et
decharger
Counter
with
the
following
screws on the trim-plate
GEH-62808
Power Break® II Circuit Breaker
Accessories
Mechanical Counter
3.
Loosen the four screws at the corners of the
breaker cover. Remove the cover from the breaker
face.
On the breaker cover, use a screwdriver to punch
4.
out the knockout above the
flag opening.
Hold the ON-OFF flag towards the ON position,
5.
field­
then carefully insert the flag lockout plate to retain
the flag in this position. The flag lockout plate
should be installed close to the side frame on
ON-OFF
which the
diameter portion of the mechanism
The installed flag lockout plate is shown in Figure
2.
Figure
2.
Flag lockout plate installed in breaker.
6.
Locate the two mounting holes through the side
frame,
behind
Place the spring-loaded Mechanical Counter arm
above
the
simultaneously
Mechanical Counter through the holes in the side
frame.
les
7.
Slide the straight legs of the provided clip over the
pin on the Mechanical Counter furthest from the
ON-OFF
flag. Rotate the clip
until the circular part of the clip snaps over the
second pin on the Mechanical Counter.
8.
Carefully remove the flag lockout plate, allowing
and
ON-OFF
the
installed Mechanical Counter is shown in Figure
CHARGE-DISCHARGE
flag pivots and over the larger
CHARGE-DISCHARGE
the
ON-OFF
tab
on
the
inserting
the
two pins
counter-clockwise
OFF
flag to return to the
position. The
cross
pin.
LOCKOUT
PLATE
flag.
flag,
while
on
the
3.

Advertisement

loading

Summary of Contents for GE GEH-62808

  • Page 1 GEH-62808 Power Break® II Circuit Breaker Accessories Mechanical Counter Introduction Loosen the four screws at the corners of the breaker cover. Remove the cover from the breaker The Mechanical Counter, shown in Figure can be face. 800-4000 installed in ampere frame Power Break® II On the breaker cover, use a screwdriver to punch circuit breakers.
  • Page 2 Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser's purposes, the matter should be referred to the GE Company. GE Electrical Distribution & Control General Electric Company 41 Woodford Ave., Plainville, CT 06062...