Haier AC092FEAHA Installation Manual

Mrv intelligent network convertible type air conditioner indoor unit
Hide thumbs Also See for AC092FEAHA:

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Haier AC092FEAHA

  • Page 2: Safety Precautions

    Safety Precautions Read this ìsafety precautionsî carefully and thoroughly before implementation to ensure proper installation. These precautions whose marks and contents as the following MUST be complied with for they include important points concerning safety. Contents marked with this sign concern personal safety of the user. Improper Warning! operation can cause personal death or injury.
  • Page 3: Selection Of Installation Place

    Install electrical leakage protector. Omission of installing electrical leakage protector can cause electric shock. DONíT install in place where flammable gas can easily leaks. Leakage of flammable gas can cause fire hazard. Water drainage pipe should be installed according to instructions to ensure smooth discharge of water.
  • Page 4: Installation Of Air Conditioner

    As shown in the diagram at the right, remove two screw snails as shown and take right-side intake barrier down. (AC182,242, 282FEAHA,AC182,242,282FEBHA Installation of Air Conditioner Installation in under ceiling 1. Installation of suspending bolts Installation of supporting frame for AC092,122,142,162FEAHA, AC092,122,142,162FEBHAtype should be internally suspended.
  • Page 5 Suspending bolt 40mm Supporting fram Hexagon bolt (ceiling) Insert hexagon bolt into carved fillet. Fasten hexagon bolt and fix the air conditioner. Position of suspending bolt The dotted indicates ( 10) position on the back of the unit. Cut it off to use.
  • Page 6 Note: drainage pipe should incline from higher inside to lower outside end. According to spot requirement, drainage pipe is provided by the user and connected firmly with drainage pipe equipped on the machine (pay attention to the joint to prevent from water leakage). Indoor part of drainage pipe should be made heatproof with heat insulation materials to prevent from condensation.
  • Page 7 Poor heat insulation can cause moisture condensation and result in water leakage Drainage pipe should incline from higher inside to lower outside. Correct Allowable deviation of distribution tube Seamless tube of phosphorus deoxidized copper specified for air conditioner AC092,122,142,162FEAHA AC092,122,142,162FEBHA Addition of refrigerant Note Note...
  • Page 8 External diameter of copper tube (mm) 6.35~25.4 28.6~38.1 Heat insulation of distribution tube should be done respectively in fluid and gas side. During refrigeration, temperatures in fluid and gas sides are low. To prevent moisture condensation, heat insulation measures MUST be taken to the two sides. Requirentents Note! Heat insulation measures should be taken to indoor drainage pipe to prevent moisture condensation.
  • Page 9: Electric Wiring

    Electric wiring Install electrical leakage protector. Omission of installing electrical leakage protector can cause electric shock. During wiring layout of remote controller , pay attention to consistency of connected terminals. Improper connection can cause machine defects. Centralized control signal lines and communication lines of indoor and outdoor units are nonpolar with 2 cores.
  • Page 10: Operation Control

    380-400V,3N~,50Hz outdoor power leak breaker manual switch shield layer should be connected together communication wire shield layer earth 1PH,220-230V~,50Hz indoor power leak breaker manual switch communication wire remote centralized control signal wire controller 1PH,220-230V~,50Hz (centralized controller) Wiring layout of centralized controller should be done according to installaiton manual of centralized controller Operation control Solution of group control One set of remote controller can control a group of 16 indoor unit at the most.
  • Page 11 Finishing and amendment Wires (cables between power supply and air conditioner) MUST keep clear of valves in gas side of distribution tube and distribution tubewithout heatproof materials. Melting of wire skin can cause electric shock, leakage and fire hazard. 1.Wrap tapes on distribution tube of refrigerant, wires in air conditioner room and drainage pipe after finishing these engineering.
  • Page 12: Trial Run

    1.Ensure stop valve of outdoor unit in ON status before trial run. 2.Compulsory trial run can make air conditioner run reluctantly but stop after a short while. 3.To protect compressor during start of the machine, switch its power on at time 12 hours in priority to operation.