Wiring arrangement
In following figure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.
Power supply cable
Cable clamp
Cable tie (*1)
*1: Cable ties for Drain pump unit are accessories of the Drain pump unit.
Cable ties for other optional parts are locally purchased.

6.6. External input and external output (Optional parts)

(1) External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• "Operation/Stop" mode, "Emergency stop" mode or "Forced stop" mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
connected unit
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
En-11
EMI core (accessory of
the IR receiver unit)
Clamps
DC power supply
*1
P.C.B
12 to 24V
*b
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
Load
resistance
Load
resistance
● Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
Cable tie
(*1)
*c
Ch 1
*c
Ch 3
connected unit
*c Select very low current use contacts (usable at DC12V, DC1mA or less).
*d The wiring is diff erent from Apply voltage terminals. Be suffi ciently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
Input device 1
CNA01
NOTE :
When connected to multiple indoor units directly, it will cause breakdown.
CNA03
Operation behavior
● Input signal type
The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.
DIP switch [Set 2 SW2]
OFF (Factory setting)
ON
DC power supply
12 to 24V
connected unit
*c
Ch 2
K1
K4
K2
K5
K3
K6
Input device 2
K1 to K6: Relay
(Device for DC Current)
Input signal type
Edge
Pulse
P.C.B
CNA01
P.C.B
CNA01
P.C.B
CNA01
P.C.B
CNA02
GND
*d
CNA04
P.C.B
CNA02
P.C.B
CNA02
P.C.B
CNA02
Edge
Pulse
The width of pulse
must be longer than
200msec.