Slc Capacity; Slc Performance; Led Operation - Honeywell Notifier AFP-100 Wiring Manual

Intelligent control panel slc
Table of Contents

Advertisement

SLC Capacity

1.7 SLC Capacity
The protocol selected for an SLC loop determines the maximum number of devices that can be handled by the loop (see Section 1.5,
"Polling Protocols", on page 11). Within those limits, the individual control panel may have additional restrictions. See the specific
installation manual for this information.

1.8 SLC Performance

SLC performance (Style 4, Style 6, or Style 7) depends on the configuration of the circuit and the components on the circuit (see
Table 1.2). SLC operation meeting Style 7 requirements isolates each addressable device on the SLC from faults that may occur on the
SLC.
Wiring style requirements are determined by national and local codes. Consult with the Authority Having Jurisdiction before wiring the
SLC. The table below (derived from NFPA 72-2002) lists the trouble conditions that result when a fault exists on an SLC. Additional
information is broken out in Section 2, "Wiring Requirements", on page 16, and Section 3, "Shielded Wire Termination", on page 22.
Type of Fault
Single Open
Single Ground
Short
Short and open
Short and ground
Open and ground
Communications loss
• Trouble - The control panel will indicate a trouble condition for this type of fault.
• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.

1.9 LED Operation

The table below lists the LED operation on the various devices of an SLC in CLIP (Classic Loop Interface Protocol) Mode and FlashS-
can® Mode. When switching from FlashScan® to CLIP mode, the loop circuit must be powered down for at least 30 seconds to reset
devices to CLIP mode LED operation.
Control Panel
AM2020
AFP1010
AFP-300/AFP-400
AFP-100
AIM-200
AFP-200
NFS-320, NFS2-640,
NFS-640
NFS2-3030,
NFS-3030
NOTE: In CLIP mode, the LPX-751 and HPX-751 blink GREEN in standby and stay RED when activated.
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
Style 4
Trouble
Alarm, Trouble (ground)
Trouble
Trouble
Trouble
Trouble
Trouble
Table 1.2 SLC Circuit Configuration and Performance: Style 4, Style 6, Style 7
Device
Standby
Monitor Module
Blinks RED
Control Module
Blinks GREEN
Detector
Blinks RED
Monitor Module
Blinks RED
Control Module
Blinks GREEN
Detector
Blinks RED
Monitor Module
Blinks RED
Control Module
Blinks GREEN
Detector
Blinks RED
Monitor Module
Blinks RED
Control Module
Blinks GREEN
Detector
Blinks RED
Monitor Module
Blinks RED
Control Module
Blinks GREEN
Detector
Blinks RED
Style 6
Alarm, Trouble
Alarm, Trouble (ground)
Trouble
Trouble
Trouble
Alarm, Trouble
Trouble
CLIP Mode
Activated
RED continuous
2 sec. GREEN, then OFF
RED continuous
RED continuous
GREEN continous
RED continuous
RED continuous
Blinks GREEN
RED continuous
RED continuous
OFF
RED continuous
RED continuous
GREEN continuous
RED continuous
Table 1.3 LED Operations
Style 7
Alarm, Trouble
Alarm, Trouble (ground)
Alarm, Trouble
Trouble
Alarm, Trouble
Alarm, Trouble
Trouble
FlashScan® Mode
Standby
Activated
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Blinks GREEN
RED continuous
Blinks GREEN
GREEN continuous
Blinks GREEN
RED continuous
Introduction
15

Advertisement

Table of Contents
loading

Table of Contents