INSTALLATION
Self Contained
1
Connection mains
Max. 10 A
Max. 10 A
Max. 10 A
2L 1L
N
2L 1L
N
2L 1L
N
Non-maintained
Switched maintained
Maintained
DALI
CIS/BUS/MD
+
--
DA DA
A B C D
A B C D
!
2
Connection spot
Do not connect Mains power to the A-B-C-D
terminals
3
min. 110 mm
Ø 68 mm
Ø 68 mm
Ø 68 mm
4
5-15 mm
insert
15-30 mm
push
Only self-contained luminaires
COMMISSIONING
Connect mains
230 - 240V / 50Hz
0-30%
100%
60h
60h
Wait
After 60 hours the luminaire is fully commissioned
SELFTEST SCHEDULE
1
Installation test / Inbetriebnahme / Test d'installation
Duration test after 36 hours, 3 hours.
2
Functional test
Every 7 days - 1 minute.
Autonomy test
3
Every 26 weeks, 3 hours.
DIMENSIONS
35 6
Ø100
Slave
1
FLX
SETUP
Self Contained
L
N K4 K3 K1
1
2
min. 45 mm
3
Ø 68 mm
2
SPECIAL APPLICATIONS
SR2.. G1
Corridor - Wall mounted
Ø 70 mm
5-30 mm
Option:
Ceiling adapter
EXPLANATIONS
Maintained
Non-maintained
Switched maintained
95
58
216
52
126
Slave
Base
Cover
1
Battery
Com-box
PCB (option)
Cable entry cover
Cable Cover
Com-box
Base +
(option)
Electronics
Geartray +
Electronics
2
Battery
SR2.. LENS2
SR2.. BC1
Object lighting
Corridor high ceiling
B
!
< 25 cm <
RISK GROUP 2
CAUTION Possibly hazardous optical radiation
OK
emitted from this product. Do not stare at operating lamp.
May be harmful to the eyes.
Emergency mode
Manual testing
Push test button < 1 sec. to set luminaire in test mode (5 sec. test).
In test
Setup even or odd testing schedule
Push test button > 3 sec. to enter the setup mode for even or odd testing schedule.
If LED's flash synchronously the luminare is set to even schedule.
If LED's flash alternately the luminare is set to odd schedule. Toggle between
even and odd by pushing the test button.
Failure
Reset luminaire
Push test button > 10 sec. to reset test schedule.
INSTALLATION
35 6
150
1
120
Surface Mounted
2
3
Sheathing
SR2.. EF1
4
Open area high ceiling
C
E
F
Communication
DALI
CT-NAVEO/CIS
DA DA
D C B A
Self- contained
Max. 10A
N 1L 2L
Non-maintained
Self-contained
5
Max. Ø 4mm
120
54
POWER
SUPPLY
max. Ø 13
max. Ø 10 (2X)
Wiring area
max. 3mm
!
LTC
SWL USL
– +
L N N L
Do not connect Mains power to
D C B A
D C B A
the A-B-C-D terminals
Slave
Max. 10A
Max. 10A
Max. 10A
N 1L 2L
N 1L 2L
N 1L 2L
Switched maintained
Maintained
Slave
Max. 3 Nm