Outdoor Unit
6. Capacity Correction Factor
■ Calculation of actual system capacity
1. Outdoor unit rated capacity
Q
[from specification table]
odu(rated)
2. Outdoor unit capacity at Ti, To temperature.
Q
[from capacity table]
odu(Ti, To)
3. Outdoor unit capacity correction factor
F
= Q
/ Q
(Ti, To)
odu(Ti, To)
4. Piping correction factor [from capacity correction factor table]
F
for main piping length or elevation
main (length, elevation)
: F
main (length, elevation)
F
branch (length, elevation)
5. Individual indoor unit combinational capacity
Q
= Q
idu (combi)
odu(rated)
: Q
is Capacity of individual indoor unit
idu(rated,each)
: Q
is Total sum of individual capacity for connected indoor units
idu(rated,total)
Refer to the 'Specifications' of each indoor units
6. Individual indoor unit actual capacity
Q
= Q
idu (actual)
idu(combi)
: F
main (length, elevation)
odu(rated)
is used only when the BD (Distributor Box) unit is connected.
for branch piping length or elevation
x Q
/ Q
idu(rated,each)
idu(rated,total)
x F
x F
(Ti, To)
main (length, elevation)
is used only when the BD (Distributor Box) unit is connected.
x F
branch (length, elevation)
Multiple piping type
131