BSPDxx100 Series Installation Instructions
These instructions are intended as a guide for installing the Siemens BSPD series of surge protective devices into any approved
panelboard or panel that the BSPD is qualified for. It is the installer's responsibility to ensure the proper device is selected for
the voltage system of the application.
Catalog no.
System voltage
BSPD2A100
120/240V, 1Ø, 3W*
BSPD3B100
240/120V, 3Ø, 4W
BSPD3C100
208Y/120V, 3Ø, 4W
BSPD3D100
240V, 3Ø, 3W
BSPD3E100
480Y/277V, 3Ø, 4W
BSPD3F100
480V, 3Ø, 3W
BSPD3G100
600V, 3Ø, 3W
BSPD3K100
380Y/220V, 3Ø, 4W
BSPD3L100
600Y/347V, 3Ø, 4W
BSPD3S100
400Y/230V, 3Ø, 4W
BSPD3T100
415Y/240V, 3Ø, 4W
*Can also be used on 208Y/120V, 1Ø, 3W System
The Siemens BSPD surge protector will fit any location that will accept either a Siemens 2-pole or 3-pole BL/BQD type breaker,
or (with the included adapter) any location an xGB or 3VA41 type breaker will fit. Note: Each SPD comes with an adapter. There
are two surge protector types (see Figure 1): - 2 Pole for Single Phase systems, - 3 Pole for Three Phase systems.
Kit # BSPDXGB1 is available in case the xGB/3VA41 adapter is lost or damaged. This kit contains 1 each of the 2-pole and 3-pole
adapters.
Figure 1 (in millimeters)
71.5
66.7
6.4
SIDE
Mechanical and electrical features:
An electronic alarm circuit is included on all product models.
This circuit monitors the integrity of the SPD and alerts the
user, using audible and visual means, in the event of failure.
The circuit is directly powered from the power system to
which the SPD is connected. A flashing green LED indicates
that it is operational. Upon failure of any of the MOVs in the
SPD, an intermittent audible chirp is emitted and the green
LED will change to a flashing red LED. If the user presses the
alarm silence switch/button, the audible chirp is silenced, but
the flashing red LED will remain. This is to warn the user that
the SPD has failed (and needs to be replaced) even though
the alarm has been silenced. Pressing the alarm silence
switch/button again will re-engage the audible chirp.
SCCR
Surge
(system rating)
current rating
200kA
100kA
200kA
100kA
200kA
100kA
200kA
100kA
200kA
100kA
200kA
100kA
200kA
100kA
200kA
100kA
200kA
100kA
200kA
100kA
200kA
100kA
50.1
0.8
0.8
FRONT
2-pole
BoltShield™ Surge Protective Devices BSPD Series for Panelboards | Installation Instructions
Volt.
VPR rating
Poles
code
L-N/L-G
2
A
600V
3
B
600V
3
C
600V
3
D
800V
3
E
1000V
3
F
1800V
3
G
2000V
3
K
900V
3
L
1200V
3
S
900V
3
T
900V
71.5
66.7
6.4
SIDE
3-pole
s
Other
specifications
• UL Type Designation: SPD Type 1, also
suitable for use in Type 2 applications
• Nominal Discharge Current (In): 20kA
• 2-pole and 3-pole bolt on configurations
in BQD footprint
• Flashing Dual Color LED (Green/Red)
Status Indicator
• Audible Alarm w/ Silence Switch/Button
• Form C Dry Contact, 240V AC, 1A Max,
48V DC 0.5A Max
• Pre-wired #14 AWG (solid copper stranded)
75.2
71.5
0.8
66.7
6.4
FRONT
LED
Audible
Alarm
Silence
Switch/Button
Mechanical
Indication
0.8

Advertisement

loading

Summary of Contents for Siemens BSPD 100 Series

  • Page 1 *Can also be used on 208Y/120V, 1Ø, 3W System The Siemens BSPD surge protector will fit any location that will accept either a Siemens 2-pole or 3-pole BL/BQD type breaker, or (with the included adapter) any location an xGB or 3VA41 type breaker will fit. Note: Each SPD comes with an adapter. There are two surge protector types (see Figure 1): - 2 Pole for Single Phase systems, - 3 Pole for Three Phase systems.
  • Page 2 Printed in USA Siemens Industry, Inc. purposes, the matter should be referred to the local Siemens sales office. The Order No. CBIM-BSPDI-0320 5400 Triangle Parkway contents of this Instruction manual shall not become part of or modify any prior...

This manual is also suitable for:

Bspd2a100Bspd3b100Bspd3c100Bspd3d100Bspd3e100Bspd3f100 ... Show all