TPS3 12 & TPS3 15
Surge Protective Device
User Manual - USA

Advertisement

Table of Contents
loading

Summary of Contents for Siemens TPS3 12

  • Page 1 TPS3 12 & TPS3 15 Surge Protective Device User Manual - USA...
  • Page 2: Failure To Follow These Instructions Could Result In Death Or Serious Injury

    WARNING - Hazardous Voltage & Shock Hazard Failure to Follow These Instructions Could Result in Death or Serious Injury • Only qualified licensed electricians should install or service SPDs • Hazardous voltages exist within SPDs • SPDs should never be installed or serviced when energized • Use appropriate safety precautions including Personal Protection Equipment • Failure to follow these instructions can result in death, serious injury, and/or equipment damage. • This manual shall be read in entirety prior to installing Bonding and Grounding Hazard Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electrical Code (NEC®) and all applicable codes. Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground in accordance with the NEC® and all applicable codes. During installation into an electrical system the SPD must not be energized until the electrical system is completely installed, inspected and tested. All conductors must be connected and functional including the neutral (if required). The voltage rating of the SPD and system must be verified before energizing the SPD. Failure to follow these guidelines can lead to abnormally high voltages at the SPD. This may cause the SPD to fail. The warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC®. Do Not Hi-Pot Test SPDs Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high-...
  • Page 3: Table Of Contents

    Table of Contents FAIluRe To FolloW THeSe INSTRucTIoNS coulD ReSulT IN DeATH oR SeRIouS INjuRy ......2 Do Not Hi-Pot Test SPDs ....................................2 INTRoDucTIoN ..............................1 Warning and Safety Information ................................1 Qualified Person .......................................1 Danger ........................................1 Warning ........................................1 Caution ........................................1 Do Not Hi-Pot Test SPDs ....................................1 Limited Warranty ......................................1 Unpacking and Preliminary Inspection ..............................1 Storage ........................................1 GeNeRAl INFoRmATIoN ............................ 2 Product Family Outline ....................................2 Type 1 SPD .......................................2 Internal Protection .
  • Page 4: Do Not Hi-Pot Test Spds

    This is a high quality, high energy surge suppressor designed to protect which are not covered sufficiently for the purchaser’s purposes, the sensitive equipment from damaging transient overvoltages. matter should be referred to the local Siemens sales office. Proper installation is important to maximize performance. Please Do Not Hi-Pot Test SPDs follow the steps outlined herein.
  • Page 5: General Information

    General Information Industry Standards Changes - 2009 UL 1449 Third Edition and 2008 NEC® Article 285 generated substantial Product Family Outline changes. TPS3 12 – Single Module in enclosure • The term TVSS changed to SPD TPS3 15 – Two Modules in enclosure • Types 1, 2, 3 & 4 SPDs are created • UL 1449 clamping voltage performance testing changed from Each is available with Standard modes (most common) or discrete 500A to 3,000A 10-modes (specific application). For example, TPS3 12 is a SPD in an • UL 1449 added new Nominal Discharge Current testing (I nominal, enclosure with Standard modes of protection; TPS3 L12 is a SPD with or In), which consists of more rigorous duty-cycle testing an enclosure having discrete ten mode protection. The SPD Type category is important to understand before installing The TPS3 12 & TPS3 15 families are intended for use as a Type 1 external any SPD. Type 1 and 2 SPDs are fully UL Listed devices whereas Type mount SPD. See Model Number Decoder in Table 1 (page 3). 4 SPDs are UL Recognized devices. Type 1 SPD Type 1 – Installed on line or load side of the Main Overcurrent Protection (OCP), similar to obsolete products known as Secondary Type 1 SPDs include internal overcurrent protection and have been Surge Arrestors, except now includes rigorous safety testing. Includes...
  • Page 6: Table 1: Model Number Decoder

    Table 1: Model Number Decoder TPS SERIES DESCRIPTION TPS3 12 Externally mounted SPD, single module in enclosure, standard modes of protection TPS3 L12 Externally mounted SPD, single module in enclosure, 10 modes of protection TPS3 15 Externally mounted SPD, dual replaceable modules in enclosure, standard modes of protection TPS3 L15 Externally mounted SPD, dual replaceable modules in enclosure, 10 modes of protection AVAILABLE VOLTAGES VOLTAGE CODES TPS3 12 TPS3 L12 TPS3 15 TPS3 L15 √ √ √ √ A = 240/120V Split Phase 1Ø, 3W Plus Grnd (Fig 1) √ √ √ √ B = 240/120V 3Ø, High Leg Delta (B High) (Fig 3) √ √ √ √ C = 208Y/120V 3Ø, 4W Plus Grnd (Fig 2) √ √ D = 240V 3Ø, 3W Plus Grnd (Fig4) √ √ √ √ E = 480Y/277V 3Ø, 4W Plus Grnd (Fig 2) √ √...
  • Page 7: Parallel Connection

    Caution – Ungrounded systems are inherently unstable and can There may be circumstances where Line Side installation is desirable. product excessively high line-to-ground voltages during certain fault Follow all applicable Code requirements for Line Side installation. We conditions. During these fault conditions, any electrical equipment generally recommend that the SPD be installed with a disconnecting including an SPD, may be subjected to voltages which exceed their mechanism for servicing purposes. designed ratings. This information is being provided to the user so that an informed decision can be made before installing any electrical Tip: Siemens TPS offers an optional Disconnect Switch that equipment on an ungrounded power system. has been UL evaluated as part of the SPD. This includes SCCR and Line Side suitability. If you do not use the disconnect Cascade Surge Protection option, select a disconnect switch rated for line side (UL 98) having appropriate SCCR rating including any required For optimum surge protection, cascade or staged surge suppression overcurrent protection. This may be more time consuming should be implemented at the service entrance and downstream and expensive than anticipated. The optional Disconnect...
  • Page 8: Service Clearance

    Table 2: Weight & Dimensions Overcurrent Protection SPDs draw very little current under normal conditions and conduct TPS3 12 H/W/D (in./mm.) Weight for a brief duration upon encountering a transient surge current. This SPD contain internal overcurrent and overtemperature protection to 12" x12" x 7.5" 22 lbs Standard Enclosure protect against abnormal voltage conditions. (305x305x191) (10 kg) Standard Enclosure, 400 – 500kA with Opt. 16" x 14" x 6" 32 lbs Disc. Switch (496x356x152) (14.5 kg) Supplemental overcurrent protection is not required to protect this SPD. However, connecting conductors require protection in Type 2 14" x 12" x 7" 14 lbs 4X Non-Metallic (356x305x178) (6.4 kg) or 4 applications. Follow applicable codes. 4X Non-Metallic, 400 – 500kA with Opt. 16" x 14" x 7" 21 lbs Disc. Switch (496x356x178) (9.5 kg) Voltage Rating...
  • Page 9: Terminals

    Terminals Figure 3: NEMA 3R Drain Holes Terminals will accept 14 - 2 AWG conductor and are provided for line (phase), neutral (if used), and equipment safety ground connections. 8 AWG is the minimum recommended wire size because UL testing and evaluation was performed using 8 AWG. Wire Size and Installation Torque This is a parallel-connected SPD; it is not series-connected. The size of the SPD wiring is independent of the ampere rating of the protected circuit. Recommended wire is 6 AWG for phase, neutral and ground Module Rotation Feature connections. Torque connections to 18 inch-pounds. Conductor length should be as short as possible. Installation lead wire length must be minimized because longer leads hurt performance. Lead length may be reduced by rotating If other wire sizes are used, all conductors must be the same gauge.
  • Page 10: Optional Flush Mount Installation Considerations

    The disconnect switch is mounted on DIN-rail. It may be removed by gently pulling out the mounting tab at the bottom of the switch Retro-fit to an Existing Panel with No Available Breaker Positions assembly. These can be difficult with limited options. Follow all applicable Siemens TPS is one of few SPD manufacturers that offer Disconnect Codes: Switches available as a fully UL qualified option. The Short Circuit Current Rating posted on the UL label of the SPD includes the • Consider consolidating loads in a manner that might free breaker Disconnect Switch and supercedes any rating on the individual positions.
  • Page 11: Tps3 12 And Tps3 15 Installation Instructions

    V DANGER CAUtION Hazardous voltage. CONDUCtING DIeLeCtRIC AND/OR Will cause death or serious injury. HI-pOteNtIAL teStING WILL CAUSe Keep Out. INteRNAL DAMAGe tO tpS3 UNIt. Qualified personnel only. Do not perform dielectric or high potential Disconnect and lock off all power before tests with the TPS3 unit installed.
  • Page 12: Figure 4: Electrical Drawings

    Figure 4: Electrical Drawings Figure 1 Figure 2 Figure 3 Figure 4 Phase A (BLK) Phase A (BLK) Hot (BLK) Phase A (BLK) Phase B (BLK) Phase B (ORNG) Neutral (WHT) Phase B (BLK) Neutral (WHT) Phase C (BLK) Hot (BLK) Phase C (BLK) Neutral (WHT) Phase C (BLK) Ground (GRN) Ground (GRN) Ground (GRN)
  • Page 13: Operation

    Phase A, B & c: Green LED indicators—one per phase. Green is good. information, there may be an internal logic problem and the unit Extinguished green LED indicates loss of protection. Every suppression needs replaced. If none of the LEDS are illuminated, the unit may not element in this SPD is monitored. N-G suppression element monitoring be installed correctly. For troubleshooting assistance, please contact is logic-connected to Phase A. Siemens TPS Tech Support at 888.333.3545. Service leD (red): LED illuminates in the event of problems. This Surge Counter Option indicator is logic-connected to the Phase LEDs. Should a Phase LED go out the Service LED will illuminate and the Audible Alarm will The surge counter registers the number of transient overvoltages on sound.
  • Page 14: Dry Contact Option

    An optional Remote Monitor accessory is available to provide visual of the module assembly. Remove module/backplane. Reinstall in and audible status. The Remote Monitor will consume one of the two reverse order. sets of Dry Contacts. There are no user serviceable parts inside the module. Disassembly is not permitted. Remote Monitor Accessory Modules may be returned to the factory for factory service, qualification A Remote Monitor—Model No. RMSIE (ordered separately) is available and return. Please contact Siemens TPS Tech Support at 888.333.3545 for remote annunciation. It requires a standalone 120V power source for assistance. (wall plug transformer) and uses one set of Form C dry contacts. The Remote Monitor can be configured to monitor several SPDs simultaneously. Installation is detailed in a separate document. Contact factory as appropriate.
  • Page 15: Display Replacement

    TPS3 15 Series with two modules 1.888.333.3545 The TPS3 15 features two redundant modules. One diagnostic display monitors both modules simultaneously via the parallel wire Prior to calling Siemens TPS3 Technical Support for assistance or connections between the modules. These connectors plug in to ordering parts, please have the following information available: each module, transfering information to internal logic on-board both modules.
  • Page 16 Siemens Industry, Inc. Building Technologies Division 5400 Triangle Parkway Norcross, GA 30092 888-333-3545 info.us@siemens.com 6.17.11.jb #8172...