Mitsubishi Electric FR-F862-E Instruction Manual page 20

Separated converter type, inverter for fans and pumps
Hide thumbs Also See for FR-F862-E:
Table of Contents

Advertisement

Vibration, impact
The vibration resistance of the inverter is up to 2.9 m/s
Y, Z axes. Applying vibration and impacts for a long time may loosen the structures and cause poor contacts of connectors,
even if those vibration and impacts are within the specified values.
Especially when impacts are applied repeatedly, caution must be taken because such impacts may break the installation feet.
Precautions
• Provide the enclosure with rubber vibration isolators.
• Strengthen the structure to prevent the enclosure from resonance.
• Install the enclosure away from the sources of the vibration.
2.3.2
Amount of heat generated by the inverter
Regarding the amount of heat generated in the FR-F860 series inverter
The amount of heat generated by the inverter unit and converter unit is shown in the following tables.
Inverter model
FR-CC2-C355K
FR-F862-05450
FR-CC2-C400K
FR-F862-06470
FR-CC2-C560K
FR-F862-08500
NOTE
• The amount of heat generated shown assumes that the output current is inverter rated current, and carrier frequency is 2
kHz.
Installation of the inverter and enclosure design
2
at 10 to 55 Hz frequency and 1 mm amplitude for the directions of X,
Amount of heat generated (W)
SLD
2500
2300
7300
4800
4300
3000
2600
8600
5600
5100
3700
3200
11400
7700
7000
LD
6600
7700
10200
INSTALLATION AND WIRING
2
19