Pioneer DR024GHFD18HT2 Service Manual page 13

High efficency air handler
Hide thumbs Also See for DR024GHFD18HT2:
Table of Contents

Advertisement

BLOWER
DATA
5.
Air
Handler
Motor Speed
Model
Tap(1)
CFM
-Default
Watts
Setting
CFM
Tap(2)
Watts
48K
CFM
Tap(3)
Watts
CFM
Tap(4)
Watts
Air
Handler
Motor Speed
Model
Tap(1)
CFM
-Default
Watts
Setting
CFM
Tap(2)
Watts
60K
CFM
Tap(3)
Watts
CFM
Tap(4)
Watts
[!] Required 350-450CFM/ton range.
[!] CFM means Standard Cubic Foot per Hour.
[!] When there is an electric heater, please set the fan
speed based on the air volume that the electric
heater needs (not less than 350CFM/TON).
Air Flow Table
0[0]
0.1[0.02]
0.18[0.045]
1756
1701
1626
348
357
369
1799
1746
1678
366
377
388
1828
1794
1749
376
387
401
1888
1855
1813
415
428
445
Air Flow Table
0[0]
0.1[0.02] 0.18[0.045] 0.3[0.07]
1838
1810
1770
376
387
401
1888
1855
1813
415
428
445
1971
1941
1893
472
485
501
2056
2022
1978
533
545
562
External Static Pressure
in.H2O[KPa]
0.3[0.07]
0.4[0.1]
0.5[0.12]
1579
1520
1468
378
387
395
1634
1571
1522
398
410
419
1719
1670
1633
413
428
437
1782
1735
1701
456
469
481
External Static Pressure
in.H2O[KPa]
0.4[0.1]
0.5[0.12]
1760
1670
1633
413
428
437
1782
1751
1701
456
469
481
1864
1820
1786
513
530
540
1950
1907
1878
575
592
603
[!] Airflow based upon Air Handler Unit operates at 230V
with no electric heater kit and no filter. Airflow at 208V is
approximately the same as 230V.
9
0.6[0.15]
0.7[0.17]
0.8[0.20]
1425
1386
1346
407
410
424
1449
1402
1241
428
444
440
1589
1553
1510
452
465
482
1665
1626
1585
495
510
525
0.6[0.15]
0.7[0.17]
0.8[0.20]
1589
1553
1510
452
465
482
1665
1626
1585
495
510
525
1755
1718
1673
558
568
586
1826
1801
1750
619
631
638