FieldMonitor Machinery Protection System Operation Manual
1701/05 Terminal Base plan view with modules removed
8
When you use the 1701/05 TB, you must install monitors
and transducer I/O modules or internal Proximitor modules
in pairs. Field wiring termination, buffered outputs, and the
Keyphasor output terminals are identified by slot number
and channel, where channels are identified as A or B.
Install monitors in numbered slots with their associated
I/O or internal Proximitor module in the corresponding
adjacent slot preceded by a "T". For example, a monitor
in slot 2 has its associated I/O in slot T2.
Install monitors in slots 2, 3, 4, and 5.
Install transducer I/Os or internal transducers used with
monitors in slots T2, T3, T4, and T5.
Install the FMIM in slot 1K.
Install an internal Proximitor sensor or transducer I/O
module for the TB's single Keyphasor transducer in slot
T1K.
If an internal transducer module such as a dual
Proximitor module is used, connect the proximity probe
cables to the connectors on the top of the internal
transducer module rather than to the I/O terminals on
the terminal base.