2.3

Wiring

(1) Untwist the shielded twisted pair cables after stripping its sheath.
Also, perform protective treatment of the shield to ensure that it will not make contact with the
conductive area.
Strip off the sheath for the below length. If the length of the sheath pealed is too long, a short circuit
may occur with neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose.(Do not solder it.)
Use a bar type terminal as required.
NOTE
• Ferrule terminals commercially available (as of February 2012. The product may be changed without notice.)
Cable gauge
Terminal
screw size
(mm
M2
0.3, 0.5
When using the ferrule terminal (without insulation
sleeve), take caution that the twisted wires do not come
out.
12
INSTALLATION AND WIRING
Cable sheath stripping length
5mm
Ferrule terminal model
With
2
)
insulation sleeve
AI 0,5-6WH
Manufacturer
Without
insulation sleeve
Phoenix Contact
AI 0,5-6
Co., Ltd.
Shield
(perform protective
treatment)
Sheath
Shielded twisted pair cable
Crimping tool
name
CRIMPFOX 6