Download Print this page

Advertisement

Quick Links

WL Trip Unit, PROFIBUS Communication
and Electronic Accessories
Application Guide
RELIABLE SOLUTIONS
WL Low Voltage Power
Circuit Breaker
ANSI / UL 1066 & UL 489
powerful ideas
Global network of innovation

Advertisement

loading

Summary of Contents for Siemens ANSI/UL 1066

  • Page 1 WL Trip Unit, PROFIBUS Communication and Electronic Accessories Application Guide powerful ideas RELIABLE SOLUTIONS WL Low Voltage Power Global network of innovation Circuit Breaker ANSI / UL 1066 & UL 489...
  • Page 2 Communication-capable Circuit Breaker Introduction and Overview WL Circuit Breaker PROFIBUS Profile for WL Circuit Breaker Breaker Data Adapter (BDA) Breaker Data Adapter Plus (BDA Plus) WL PROFIBUS Communication and Electronic Accessories • July 2004...
  • Page 3 Registered Trademarks WinPM.Net is a registered trademark of Siemens Energy & Automation. Some other designations used in these documents are also brands; the owner's rights may be violated if they are used by third parties for their own purposes.
  • Page 4 Introduction and Overview Content of the Manual Overview of the Bus Systems Communicating with the Circuit Breaker WL PROFIBUS Communication and Electronic Accessories • July 2004...
  • Page 5 Introduction and Overview WL Circuit Breaker General This manual is aimed at those Content of the Manual Introduction who want to find out more Chapter 1 contains a short The demand for communications- introduction to communications capable systems, data transparency about the different applications in power distribution systems, and and flexibility in industrial automation...
  • Page 6 Introduction and Overview WL Circuit Breaker In this way, status information, WL Circuit Breakers—Modular and alarms, trip information and Intelligent setpoints (e.g. overcurrent, phase Thousands of options with just a few unbalance, overvoltage) increase components: That's the WL. A new transparency in power distribution generation of circuit breakers –...
  • Page 7 Introduction and Overview WL Circuit Breaker Communication Bus Systems Communication bus systems PROFIBUS The protocol used by the PROFIBUS-DP stations supports communication are used to connect distribution The PROFIBUS-DP is an open, between the complex, equal- standardized, multi-vendor field devices with varying levels priority programmable controllers bus system.
  • Page 8 Introduction and Overview WL Circuit Breaker • Pure master-slave system Acyclic data transmission is carried out via DPV1. The existing PROFIBUS • Pure master-slave system with standard has been extended to token passing include DPV1 with a number of • A system combining both additional functions.
  • Page 9: Profibus-Dp

    SIMATIC NET is based on this tried- intelligence. LONs are mainly used After a random time has elapsed, the and-tested technology. Siemens for building system automation and sender restarts the send operation. are often implemented in the...
  • Page 10 Communication-capable Circuit Breakers WL Circuit Breaker Modbus Modbus is an open, serial communuciations protocol based on a master-slave architecture. Since it is very easy to implement on any kind of serial interface, it can be used in a wide range of applications. Modbus comprises a master and several slaves, whereby comunication is controlled exclusively by the master.
  • Page 11 Communication-capable Circuit Breakers WL Circuit Breaker Communication Structure of the Starting at the lowest level with WL Circuit Breakers simple configuration of the circuit breakers, to the field level with The following diagram: a PLC and WinPM.Net software • Provides an overview of the tool, to a connection to the different communication options Intranet/Internet, the potential for...
  • Page 12 WL Circuit Breaker Short description of WL Circuit Breaker The CubicleBUS Communication Function of the Trip Units The COM15 PROFIBUS Module Metering and Metering Plus Description of Important Functions/Parameters for Communication External CubicleBUS Modules External Power Consumption of a WL Circuit Breaker with CubicleBUS WL PROFIBUS Communication and Electronic Accessories •...
  • Page 13 Communication-capable Circuit Breakers WL Circuit Breaker Introduction and Overview The demands regarding Brief Description of the WL Circuit Breaker family kA to be interrupted WL Circuit Breaker have a lot to offer: reliably. communications It is possible to carry out Circuit breakers today are WL Circuit Breakers can be capability, data...
  • Page 14 Communication-capable Circuit Breakers WL Circuit Breaker Communications Capability of the The ability to change between The CubicleBUS two different parameter sets is also Electronic Trip Units (ETUs) The CubicleBUS, which connects all possible. This function is particularly The electronic trip units ETU745, the intelligent components within useful in the event of a power ETU748, ETU755, and ETU776 are...
  • Page 15 Communication-capable Circuit Breakers WL Circuit Breaker Functional overview of the trip unit system Basic Functions ETU725 ETU727 ETU745 Long-time overcurrent protection Function can be switched ON/OFF – – – Setting range I R = I n x … 0.4, 0.45, 0.5, 0.55, 0.4, 0.45, 0.5, 0.55, 0.4, 0.45, 0.5, 0.55, 0.6, 0.6, 0.65, 0.7, 0.8,...
  • Page 16 Communication-capable Circuit Breakers WL Circuit Breaker Basic Functions ETU725 ETU727 ETU745 Parameter sets Selectable between parameter set A and B – – – LCD, alphanumeric (4-line) – – LCD, graphic – – – Communication CubicleBUS integrated – – Communication capability via PROFIBUS –...
  • Page 17 Communication-capable Circuit Breakers WL Circuit Breaker Functional overview of the trip unit system Basic Functions ETU748 ETU755 ETU776 Long-time overcurrent protection Function can be switched ON/OFF – – – Setting range I R = I n x … 0.4, 0.45, 0.5, 0.55, 0.4 …...
  • Page 18 Communication-capable Circuit Breakers WL Circuit Breaker Basic Functions ETU748 ETU755 ETU776 Parameter sets Selectable between parameter set A and B – LCD, alphanumeric (4-line) – – LCD, graphic – – Communication CubicleBUS integrated Communication capability via PROFIBUS Metering function Metering function capability with Metering Function or Metering Function PLUS Display by LED...
  • Page 19 Communication-capable Circuit Breakers WL Circuit Breaker Data Availability on the CubicleBUS If a data source (module) does not exist, the data point does not exist either. All modules connected to the CubicleBUS can request data from other modules via the bus and generate data Again, the relevant property byte contains this themselves that can be read by other modules.
  • Page 20 Communication-capable Circuit Breakers WL Circuit Breaker The PROFIBUS COM15 Module and the BSS Interposing relays must be used if The COM15 module enables the If required, control/write access to the opening and closing solenoids the circuit breaker can be locked WL Circuit Breaker to exchange are designed for voltages other than using hardware and software to...
  • Page 21 Communication-capable Circuit Breakers WL Circuit Breaker PROFIBUS Installation Guideline The Com15 must be assembled and connected to the PROFIBUS as described in the PROFIBUS Installation Guideline (Order No. 2.112 from the PROFIBUS User Organization www.profibus.com). Of particular importance is the requirement to ground the shield of the PROFIBUS cable.
  • Page 22 Communication-capable Circuit Breakers WL Circuit Breaker The write-protect function ensures that all the required information can be transmitted, but prevents any changes to the status of the circuit breaker. Changes can then only be made locally. Why does the write protection function permit certain actions? All actions that are not blocked are for remote analysis only and do not have any effect on the...
  • Page 23 Communication-capable Circuit Breakers WL Circuit Breaker are actuated. “Circuit breaker fully PROFIBUS LED Meaning withdrawn” is communicated No voltage on the COM15 module immediately on the cyclic channel and in the DPV1 data sets. Bus error Communication not possible The sequence described above No communication with class 1 master provides hysterisis for communicating Green...
  • Page 24 Communication-capable Circuit Breakers WL Circuit Breaker The BSS indicates the following Breaker Status Sensor (BSS) If the status of the circuit breaker information: in the switchgear is to be displayed BSS stands for “breaker status or read via communications, the •...
  • Page 25 Communication-capable Circuit Breakers WL Circuit Breaker Metering Function and Metering Function Plus The integrated metering function General The metering function module is installed on the back of the trip unit In addition to the current values can be used with all trip units (ETU), as shown in Fig.
  • Page 26 Communication-capable Circuit Breakers WL Circuit Breaker Metering Function Plus The Metering Function Plus module extends the range of metering functions to include harmonic and waveform analysis. Harmonic analysis The Metering Function Plus module senses the current and voltage, saves the measured values, and carries out a fast Fourier transformation.
  • Page 27 Communication-capable Circuit Breakers WL Circuit Breaker The trigger event can be set voltage transformer must be For a 14AWG cable, the maximum individually for each waveform used. The burden of the metering distance should not exceed 50 m buffer. The point at which the function is 27kΩ, which means for class 0.5 and 100 m for class 3.
  • Page 28 Communication-capable Circuit Breakers WL Circuit Breaker The metering function provides the following measured values for communication system: Measured value Value range Accuracy (with direct order: circuit breaker + trip unit + met. function or met. function Plus) Currents I 30 ... 8000A ±...
  • Page 29 Communication-capable Circuit Breakers WL Circuit Breaker The extended protective relay functions of the metering function can monitor the following criteria and initiate a trip if values are exceeded. Protective Relay Function ANSI Device Number Setting range Possible delay Current unbalance 5 ...
  • Page 30 Communication-capable Circuit Breakers WL Circuit Breaker Important functions/parameters for communications Thanks to their modular The respective process for the load Load Management restore threshold is reversed if all A circuit breaker with ETU745 or construction and numerous I/O three phases fall short of the higher, offers two current setpoint modules, WL Circuit Breakers setpoint, and a load shed warning...
  • Page 31 Communication-capable Circuit Breakers WL Circuit Breaker Setpoints The trip log is similar to the event The measured real power is either log, however, only the last 5 trips assigned to a positive polarity (in In addition to the load management are recorded with a time stamp normal direction) or a negative option (load shedding/load restore),...
  • Page 32 Communication-capable Circuit Breakers WL Circuit Breaker External CubicleBUS Modules Installation By connecting additional, Rotary Switches The external CubicleBUS modules external modules to the With the exception of the can be installed onto a standard configurable output module, all CubicleBUS, breaker status 35mm DIN rail on the panel.
  • Page 33 Communication-capable Circuit Breakers WL Circuit Breaker Power Supply Maximum CubicleBUS Configuration CubicleBUS Installation Guidelines The CubicleBUS must be supplied The CubicleBUS can comprise up to 13 • Total length of the CubicleBUS with a UL Listed 24V DC class 2 modules: cables: max.
  • Page 34: Device Led

    Communication-capable Circuit Breakers WL Circuit Breaker • The ZSI module must be the first DEVICE LED Meaning external module to be connected, if used. Internal error in the CubicleBUS module • If the BDA is connected to the Yellow CubicleBUS module in test mode front interface of the trip unit, the cable must be no longer Green...
  • Page 35 Communication-capable Circuit Breakers WL Circuit Breaker Testing the Digital Input and Pressing the “Test” key several times The inputs on the input module, Output Modules in quick succession then switches the outputs on the output module, the corresponding input or output ON ZSI input, and the ZSI output can be The test should be performed prior and OFF alternately.
  • Page 36 Communication-capable Circuit Breakers WL Circuit Breaker Since the CubicleBUS is event Digital Input Module Functional description for controlled, trip unit ETU755 or changing parameter sets Functional description ETU776 switches over to the other Trip units ETU755 and ETU776 have The digital input module enables up parameter set when a switchover two different parameter sets for the to six additional binary signals (24V...
  • Page 37 Communication-capable Circuit Breakers WL Circuit Breaker Digital Output Module with Selector switch position to the left Delay time Rotary Switch If the rotary switch is positioned The rotary switch can also be used to The digital output module can be to the left, outputs 1 through 6 set an additional delay time.
  • Page 38 Communication-capable Circuit Breakers WL Circuit Breaker Configurable Digital Output These events are available for the digital, configurable output module (part 1) Module Circuit breaker closed The configurable digital output module also has six outputs. Like Circuit breaker open the digital output module with the Storage spring charged rotary switch, it is available with Ready-to-close...
  • Page 39 Communication-capable Circuit Breakers WL Circuit Breaker The status can be read via the input These events are available for the digital, configurable output module (part 2) module, which means that a motor could be switched ON or OFF via the Over current configurable digital output module.
  • Page 40 Communication-capable Circuit Breakers WL Circuit Breaker A01: Active power phase kW Analog Output Module Since the circuit breaker can be designed for different rated A02: Active power phase kW The analog output module can be currents, the full-scale value must used to output the most important A03: Active power phase kW be scaled automatically and the...
  • Page 41 Communication-capable Circuit Breakers WL Circuit Breaker A01: Network frequency The test mode is started by pressing • By repeating the above steps, the “TEST” key and indicated by the the output and scaling of all four A02: Average value of the phase- yellow DEVICE LED.
  • Page 42 Communication-capable Circuit Breakers WL Circuit Breaker Short-circuit at 3: ZSI Module • If the short-circuit did occur in the downstream level, the upstream To use the ZSI function with the Circuit breakers -Q5, -Q3, and -Q1 circuit breaker delays tripping to establish that a short-circuit has WL Circuit Breaker, the external ensure that the circuit breaker...
  • Page 43 Communication-capable Circuit Breakers WL Circuit Breaker Short-circuit at 1: The ZSI module must always be the Active inputs and outputs are first external CubicleBUS module to indicated by a yellow LED. Only -Q1 establishes that a short- be connected to the COM15 module It is recommended that the ZSI signal circuit has occurred and does not or to X8.
  • Page 44 Communication-capable Circuit Breakers WL Circuit Breaker Graphic 2-7 This diagram consists of two parts: the top half is a connection diagram. The bottom half shows the circuitry when a tie breaker is used. 2/32 WL PROFIBUS Communication and Electronic Accessories • July 2004...
  • Page 45 Communication-capable Circuit Breakers WL Circuit Breaker External power consumption of a WL Circuit Breaker with CubicleBUS If additional CubicleBUS components WL Circuit Breakers with already activated and monitor the are applied on a WL Circuit Breaker, current at minimum values of 80A CubicleBUS are designed to the breaker must be connected to for Frame Size II, and 150A for...
  • Page 46 WLSITOP1 power supply: • First, the maximum continuous Table 2-24 A Siemens power supply can be selected for one or more WL Circuit Breakers. current which the CubicleBUS modules draw from the CubicleBUS supply must be calculated. (see Table 2-23) •...
  • Page 47 Communication-capable Circuit Breakers WL Circuit Breaker Notes 2/35 WL PROFIBUS Communication and Electronic Accessories • July 2004...
  • Page 48 PROFIBUS Communication with WL Circuit Breakers How to integrate the circuit breaker into PLC’s PROFIBUS Profile for the WL circuit breaker Data transmission via DPV1 Diagnostic Programming samples WL PROFIBUS Communication and Electronic Accessories • July 2004...
  • Page 49: Profibus-Dp

    PROFIBUS Communication WL Circuit Breaker Integration into an Automation System A wide range of options are Communication Options The PROFIBUS COM15 module available for integrating WL acts as an interface between the circuit breakers in automation circuit breakers and the information environment.
  • Page 50 To run the slave on the PROFIBUS-DP, for WL circuit breakers from the DP\Other field devices\Switchgear.” you still have to assign and set a Siemens A&D Service and Support Note: The GSD file can be used for unique address on this PROFIBUS-DP Homepage.
  • Page 51 PROFIBUS Communication WL Circuit Breaker Figure 3-1 You can use the STEP7 hardware configuration tool to configure the S7 automation system and its field buses. To add a circuit breaker, you have to configure either a CPU with an integrated PROFIBUS-DP interface or a PROFIBUS-DP CP card in the rack and then assign it to the PROFIBUS-DP. Note: You do not have to take the settings on the “Hex parameterization”...
  • Page 52 PROFIBUS Communication WL Circuit Breaker Figure 3-3 Once you have selected the basic type, a SENTRON circuit breaker icon appears next to the PROFIBUS-DP. In the lower part of the split window, you can/must set the S7 input/output address that can be accessed in the STEP7 program. WL PROFIBUS Communication and Electronic Accessories •...
  • Page 53 PROFIBUS Communication WL Circuit Breaker Graphic 3-2 The 3-stage communication concept not only enables quick and easy access, but also ensures that the system can be adapted for more complex demands. Stage 1 is standard; stages 2 and 3 optional. The 3-Stage Communication Concept Stage Stage...
  • Page 54 PROFIBUS Communication WL Circuit Breaker Setting the PROFIBUS Address for the COM15 Module The PROFIBUS-DP address is stored in the COM15 PROFIBUS-DP module on the circuit breaker. The system is shipped with the default address 126. All the stations on the PROFIBUS-DP must have a unique address, which means that a new address must be assigned when the PROFIBUS-DP...
  • Page 55 PROFIBUS Communication WL Circuit Breaker Changing the address via the BDA Changing the address via DS160 or BDA Plus (see also Chapter 4) The PROFIBUS-DP address of the Once a connection with the circuit appropriate slave is located in data breaker has been established (e.g.
  • Page 56 PROFIBUS Communication WL Circuit Breaker PROFIBUS Profile for Circuit Breakers The PROFIBUS User Organization This type of transmission is only As a result, WL circuit breakers required occasionally and should be communicate using state-of-the- promotes the use of joint, multi- taken into account for each message, art technology.
  • Page 57 PROFIBUS Communication WL Circuit Breaker Byte Definition of basic type 1 Byte Definition of basic type 2 Byte Definition of basic type 3 Binary status information Binary status information Binary status information Data block 1 Data block 1 Data block 1 Data block 2 Data block 2 Data block 2...
  • Page 58 PROFIBUS Communication WL Circuit Breaker Byte Default assignment basic Byte Default assignment basic Byte Default assignment basic type 1 type 2 type 3 Binary status information Binary status information Binary status information Current in Phase 1 Current in Phase 1 Current in Phase 1 Current in Phase 2 Current in Phase 2...
  • Page 59 PROFIBUS Communication WL Circuit Breaker Pre-Assignment of the Three Property Byte (PB) Basic Type 2 Basic Types In each of the basic types, the Basic type 2 comprises 8 data blocks, Once a basic type has been selected assigned data blocks are followed which are pre-assigned for a WL with the PROFIBUS-DP master by the accompanying property...
  • Page 60 PROFIBUS Communication WL Circuit Breaker Binary Status Information in the data message, irrespective of the Cyclic Channel basic type that has been selected. The binary status information in the The binary status information cyclic channel is transmitted each comprises two bytes (not one word, time data is exchanged.
  • Page 61 PROFIBUS Communication WL Circuit Breaker Control Bytes information on the precise It is sufficient to set the bits for all assignment of the write protection the controllers to between 0.5 and The three basic types differ with inputs (DPWriteEnable), reference 5 seconds because setting the output regard to the quantity and content Chapter 2.
  • Page 62: Sync And Freeze

    PROFIBUS Communication WL Circuit Breaker The following control functions are The UNFREEZE control command SYNC and FREEZE cancels the FREEZE mode of the available even without a bridge: The PROFIBUS-DP features addressed DP slaves so that they • Change and set the trigger functions the control commands SYNC resume cyclic data transmission for the waveform buffer...
  • Page 63 PROFIBUS Communication WL Circuit Breaker Shortly before 30 minutes have Diagnosing the WL Circuit Breaker Diagnostic Message elapsed (29:50), a SYNC command In accordance with the relevant By requesting the diagnostic data, is sent to all the devices in question. standards, the slave reports an the DP master checks at start-up The bit for synchronizing the clocks...
  • Page 64 PROFIBUS Communication WL Circuit Breaker Structure of the PROFIBUS Diagnostic Function Part of the diagnosis Byte.Bit Meaning for WL Station status 1 Station status 2 Station status 3 DP Standard PROFIBUS master address ID no. of high byte (0x80) ID no. of low byte (0xC0) 0x42 fixed 0x00 when no device-specific diagnosis is present 0x01 when a device-specific diagnosis is present...
  • Page 65 PROFIBUS Communication WL Circuit Breaker Explanation of bytes 20 to 27 in the WL diagnostic message Byte/Bit 20/24 Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Metering Analog Analog ETU776 function or output output graphic...
  • Page 66 PROFIBUS Communication WL Circuit Breaker Note: The value specified for parameter “IOID” depends on the logical base address “LADDR.” The smaller input or output address, which is displayed or was entered under DP Slave Properties on the “Address / ID” tab page, is always used as the logical base address.
  • Page 67 PROFIBUS Communication WL Circuit Breaker Example: Reading and Writing Data Records with an S7 This example is based on an S7-300 CPU with an integrated DP interface and STEP7 Version 5.1. Writing data records In this example, SFC58 is used to write the protection parameters to DS129.
  • Page 68 PROFIBUS Communication WL Circuit Breaker Figure 3-12 It has recently been decided to issue separate certificates for SENTRON WL and SENTRON VL. It used to be the case that two products tested in two different test centers (Furth, Germany, and Johnson City, USA) were issued a common PROFIBUS certificate. 3/20 WL PROFIBUS Communication and Electronic Accessories •...
  • Page 69 Breaker Data Adapter (BDA) Breaker Data Adapter Plus (BDA Plus) Short Description of the BDA/BDA Plus System Requirements Connect the BDA/BDA Plus to the WL Circuit Breaker Communication via the Serial Interface Communication via the Ethernet Interface Operating Instructions Troubleshooting WL PROFIBUS Communication and Electronic Accessories •...
  • Page 70 Breaker Data Adapter (BDA) WL Circuit Breaker Brief Description and System Requirements The Breaker Data Adapter (BDA) CubicleBUS module. The indicator Benefits of the BDA: with the browser application (e.g. • No special software has to be is the first circuit breaker laptop) is connected to the BDA installed;...
  • Page 71 Breaker Data Adapter (BDA) WL Circuit Breaker BDA in Offline Mode (or BDA Plus) In offline mode, the BDA or BDA Plus is only connected to a laptop (represents all input/output devices). All the required parameters can be set in this operating mode and saved for later use (download to the circuit breakers).
  • Page 72 Breaker Data Adapter (BDA) WL Circuit Breaker BDA Plus as an Ethernet Interface In addition to the previously mentioned functions, the BDA Plus enables data to be accessed via the Ethernet. In this case, the circuit breaker data is not transmitted as net data, but displayed on HTML pages in an application-specific format.
  • Page 73 Breaker Data Adapter (BDA) WL Circuit Breaker Circuit breaker requirements System Requirements However, the same Java applet can run on all supported systems Certain prerequisites have to be The BDA can be connected to WL without modifications. Circuit Breakers with the following fulfilled before the BDA or BDA trip units: ETU745, ETU748, ETU755 Plus can be operated.
  • Page 74 Breaker Data Adapter (BDA) WL Circuit Breaker Connection to WL Circuit Breakers To operate the BDA, it must be Permanent used for permanent installation. The DIN rail installation kit supplied The trip unit interface through the connected to the target system is used to secure the device.
  • Page 75 Breaker Data Adapter (BDA) WL Circuit Breaker Operation As a microcomputer, the BDA is booted in the same way as a PC. This takes approximately 40 seconds and is started automatically when the power supply is switched on. During this time, the content is loaded from the Flash memory to the main memory, an internal self test is carried out, the operating...
  • Page 76 CubicleBUS of the WL, it must be 3W / 5W / 7W activated via an external 24V DC Dimensions W/H/D 82mm /153mm / 38mm power supply. Siemens SITOP 24V DC power supplies are suitable 0.38 kg Weight for this purpose.
  • Page 77 Breaker Data Adapter (BDA) WL Circuit Breaker Connection to the BDA via the Serial Communication System been established correctly. Once To operate the BDA, it must be They are shown as a reference. you have opened the entry screen The screenshots on the following connected to the target system (Start >...
  • Page 78 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-5 Installing a standard modem with Windows98, part 1 (identical to Windows95, WindowsNT and WindowsME): A standard modem (28800 bps) is selected and installed in the Control Panel. The automatic identification function must be switched off for this purpose.
  • Page 79 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-6 Installing a standard modem with Windows98, part 2 (identical to Windows95, WindowsNT and WindowsME): Once you have installed the standard modem, you have to set it to the maximum rate of 115200; the default settings in the other windows are retained.
  • Page 80 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-7 Installing a data communications connection to the BDA with Windows98, part 1 (identical to Windows95 and WindowsME): You now have to establish a data communications connection to the BDA. To do so, double-click “Establish New Connection” in the Control Panel and then maintain the windows as shown.
  • Page 81 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-8 Installing a data comm. connection to the BDA with Windows98, part 2 (identical to Windows95 and WindowsME): Once communication has been established, the connection window disappears from the Windows systray. To display the BDA pages, enter address 2.2.2.1 in the browser.
  • Page 82 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-10 Installing a standard modem with Windows2000, part 2 (identical to WindowsXP): Select the standard modem (28800) and assign it to a free COM interface. 4/13 WL PROFIBUS Communication and Electronic Accessories • July 2004...
  • Page 83 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-11 Installing a standard modem with Windows2000, part 3 (identical to WindowsXP): After installation, you have to set the maximum rate to 115200. This completes the installation procedure. 4/14 WL PROFIBUS Communication and Electronic Accessories • July 2004...
  • Page 84 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-12 Setting up a data communications connection to the BDA with WindowsXP, part 1: Go from the Control Panel to “Network Environments” and click “Establish New Connection,” as shown above. Then follow the instructions provided by the Installation Wizard.
  • Page 85 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-13 Setting up a data communications connection to the BDA with WindowsXP, part 2: Continue following the instructions and maintain the windows as shown above. 4/16 WL PROFIBUS Communication and Electronic Accessories • July 2004...
  • Page 86 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-14 Setting up a data communications connection to the BDA with WindowsXP, part 3: Once the data communications connection has been successfully set up, WindowsXP establishes a connection with the BDA when you click “Dial.” 4/17 WL PROFIBUS Communication and Electronic Accessories •...
  • Page 87 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-15 Setting up a data communications connection to the BDA with WindowsXP, part 4: Once the connection has been established, start the browser and enter the address 2.2.2.1. To display the connection properties so that you can check them, double-click the appropriate icon in the systray.
  • Page 88 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-16 Setting a data communications connection to the BDA with Windows2000, part 1 (similar to WindowsNT): A modem is installed for Windows2000 in the same way as for WindowsXP. You then have to set up the data communications connection to the BDA. To do so, proceed as shown in the screenshots.
  • Page 89 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-17 Setting up a data communications connection to the BDA with Windows2000, part 2 (similar to WindowsNT): The procedure for setting up the data communications connection for WindowsNT is largely the same as the example shown above for Windows2000. 4/20 WL PROFIBUS Communication and Electronic Accessories •...
  • Page 90 Breaker Data Adapter (BDA) WL Circuit Breaker Figure 4-18 Setting up a data communications connection to the BDA with Windows2000, part 3 (similar to WindowsNT): Once the installation is complete and the connection has been established via the null modem cable, start the browser by entering the address 2.2.2.1.
  • Page 91 Breaker Data Adapter (BDA) WL Circuit Breaker Connection to the BDA Plus via the Ethernet Interface Ethernet/Intranet lines are In addition to communication If a sender has started sending, connected to each other using it checks that the message it has via the serial RS232 channel, the repeaters, bridges/switches, routers sent is not corrupt.
  • Page 92 Breaker Data Adapter (BDA) WL Circuit Breaker Gateway IP Address IP Addresses Subnet Mask The partner must have a unique If an address that is not located in The subnet mask provides the subnetwork is addressed in the address so that it can be addressed information on the size of the browser, the request is forwarded in the extensive Intranet/Internet...
  • Page 93 Breaker Data Adapter (BDA) WL Circuit Breaker Operating Instructions and Troubleshooting The BDA supports state-of-the- whether it is available, or readable Online mode and/or writable. The display then art communications technology. Online mode is activated changes depending on the automatically when the BDA is It can be implemented property byte.
  • Page 94 Once you have entered at 1-800-964-4114 loaded to the device have actually the password successfully, the data seainfo@sea.siemens.com been transferred. This is because, is transmitted to the circuit breaker. for example: If you want to reset the modified •...
  • Page 95 Breaker Data Adapter (BDA) WL Circuit Breaker Advantages through communication Troubleshooting List Fault Description Solution Ensure that you are using a fully-assigned null modem cable. With a null modem cable, pins 2 and 3, 4 and 6, and 7 and 8 must be assigned and reversed with respect to each other.
  • Page 96 © 2004 Siemens Energy & Automation, Inc. All Rights Reserved Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. Order # CBCM-02000-0704...

This manual is also suitable for:

Ansi/ul ul489