Section 2 Safety Precautions
Do not replace expansion unit unless power has been switched off or the area is
known to be non-hazardous.
NE REMPLACEZ L'UNITÉ D'EXTENSION QUE SI LE
COURANT A ÉTÉ COUPÉ OU SI LA ZONE EST JUGÉE NON DANGEREUSE.
This product contains a battery; this must only be changed in an area known
to be non-hazardous.
Replace the battery with a BR 2032 battery. Use of another type of battery
may present a risk of fire or explosion.
Battery may explode if mistreated. Do not recharge, disassemble or dispose
of in fire.
LA BATTERIE PEUT EXPLOSER EN CAS DE MAUVAISE MANIPULATION.
NE LA RECHARGEZ PAS, NE LA DÉMONTEZ PAS ET NE LA JETEZ
PAS DANS LE FEU.
For use on a flat surface of a type 4X enclosure indoor use only.
Use minimum 75°C copper conductors only.
To make wiring connections to the power supply connector, follow the table with
cable and torque specifications below:
Terminal Block Connector
X1/X100 Phoenix connectors
X1/X100 Anytek connectors
These devices are Class 2 supplied programmable controllers (industrial PCs)
for the use in industrial control equipment and are intended to be (front) panel
mounted (Type 1 and 4x for indoor use only).
The enclosure provides a degree of protection of at least IP20, but when installed
in an apparatus, it should meet IP54.
LE BOÎTIER OFFRE UN DEGRÉ DE PROTECTION D'AU MOINS IP20, MAIS
LORSQU'IL EST INSTALLÉ DANS UN APPAREIL, IL DOIT ÊTRE DE CLASSE IP54.
3BSE069462-600 Rev D
UL and cUL Installation
Wire Size
AWG 30–12
AWG 24–12
TQ
5–7 Lb.In.
3.5 Lb.In.
13