About this guide This guide contains the basic procedure that needs to be followed to start up an ACS850 drive (with Standard Control Program). During the procedure, the drive is set up using the ACS850 Control Panel. Note: Only the functions of the Control Panel needed during the procedure are described in the guide.
4 Quick Start-up Guide for ACS850 with Standard Control Program Start-up procedure Safety The start-up may only be carried out by a qualified electrician. The safety instructions must be followed during the start-up procedure. See the safety instructions on the first pages of the appropriate hardware manual.
Page 5
Quick Start-up Guide for ACS850 with Standard Control Program 5 To adjust a parameter within an assistant: • Use the keys to adjust the setting. Press SAVE to accept the setting shown and to proceed to the next parameter. To adjust a parameter at any other time: •...
Page 6
6 Quick Start-up Guide for ACS850 with Standard Control Program PAR GROUPS Navigate to parameter group 99 Start-up data and 99 Start-up data press SEL. Note that the list will wrap around in 01 Actual values either direction between groups 99 and 01 – it is...
Quick Start-up Guide for ACS850 with Standard Control Program 7 Application macros are pre-defined parameter Parameter defaults for the macro settings that can be used as a basis for user are applied. applications. The following macros are available: • Factory (for speed control applications where a simple start/stop interface is required) •...
Page 8
8 Quick Start-up Guide for ACS850 with Standard Control Program Select the motor control mode. DTC is suitable for 99.05 Motor ctrl mode most cases. Scalar mode is recommended if • the nominal current of the motor is less than 1/6 of the nominal current of the drive, •...
Page 9
Quick Start-up Guide for ACS850 with Standard Control Program 9 • motor nominal voltage 99.07 Mot nom voltage Allowed range: 1/6 × U … 2 × U of the drive. (U refers to the highest voltage in each nominal voltage range).
Page 10
10 Quick Start-up Guide for ACS850 with Standard Control Program • maximum torque 20.07 Maximum torque1 For the Normal ID run (see below), this value should be at least 100% of motor nominal torque defined earlier. • minimum torque 20.08 Minimum torque1 The question “Do you want to perform id-run now?”...
Page 11
Quick Start-up Guide for ACS850 with Standard Control Program 11 The STANDSTILL ID run should be selected only if the Normal or Reduced ID run is not possible due to the restrictions caused by the connected mechanics (e.g. with lift or crane applications).
Page 12
12 Quick Start-up Guide for ACS850 with Standard Control Program 3-wire: Start/Stop commands are determined on the basis of the two sources selected by parameters 10.02 and 10.03. State of source 1 State of source 2 Command (via par. 10.02) (via par.
Page 13
Quick Start-up Guide for ACS850 with Standard Control Program 13 After the text “Done OK” appears on the control panel, press OK to complete the firmware assistant. 4 – Reference selection MAIN MENU In the Main menu, highlight ASSISTANTS and press PARAMETERS ENTER.
Page 14
14 Quick Start-up Guide for ACS850 with Standard Control Program You are now asked if each constant speed selector should activate one constant speed. No: Constant speeds 1…7 are activated by the sources selected by parameters 26.02, 26.03 and 26.04 as follows:...
Page 15
Quick Start-up Guide for ACS850 with Standard Control Program 15 Select the source to switch between acceleration/ 22.01 Acc/Dec sel deceleration ramp pairs 1 and 2. 0 = Acceleration time 1/Deceleration time 1 are in force, 1 = Acceleration time 2/Deceleration time 2 are in force.
Page 16
16 Quick Start-up Guide for ACS850 with Standard Control Program Define the scaled values that correspond to the 13.04 AI1 max scale or maximum and minimum values defined at the 13.09 AI2 max scale previous step. This is useful if full speed is required 13.05 AI1 min scale or...