Installation Instruction
RSC (0,25 Nm)
DE – Kodierung
EN – Coding
Fernmeldekontakt / Remote Signalling Contact
5SD7 483-4
RSC
12
11
14
7mm
0.14 mm
Safety
instructions
see back view
5SD7 483-3 / 5SD7 483-4
5SD7 498-1
5SD7 498-2
5SD7 498-1
4,5 Nm
U
/I
max
max
AC: 250 V/ 1 A
U
/I
max
max
DC: 125 V/ 0.2 A
7mm
2
2
- 1.5 mm
MLFB
Anforderungsklasse / Requirement class
Max. Stringspannung U
/
OC STC
Max. string voltage U
OC STC
Max. Kurzschlussstrom I
/
SC STC
Short circuit current I
SC STC
Nennstoßstrom I
(8/20)μs /
n
Nominal discharge current I
(8/20)μs
n
Max. Ableitstoßstrom I
(8/20)μs /
max
Max. discharge current I
(8/20)μs
max
Schutzpegel U
/ Protection level U
p
p
Temperaturbereich /
Operating temperature range
Schutzart / Degree of protection
∅ min. L, PE, N
∅ max. L, PE, N
Ersatzstecker / Replacement
Installation
!
Photovoltaic Application
L+
L-
6
L-
L+
L-
L+
L
N PE
5SD7 483-3 / 5SD7 483-4
C acc. to E DIN VDE 0675-6;
SPD class II acc. to IEC 61643-1;
SPD Type 2 acc. to EN 61643-11
1000 V DC
80 A DC
15 kA
30 kA
≤ 5 kV ((L+)-(L-)) / ≤ 3 kV ((L+/L-)-PE)
-40 ... +80 °C
IP20
2
16 mm
16 mm
2.5 mm
2
35 mm
5SD7 498-1 / 5SD7 498-2
transparent ⇒ ok
red ⇒ defect
Recycling
Photovoltaic
Generator
−>
I
max.
80 A
DC (SC STC)
U ocstc
1000V
DC max
L+
L-
T o converter
1000 V
Switch
Converter
Z-NR: 9049753_01/8.1.10 Printed in Germany
253676.41.90 "02"
2
2.5 mm
2
25 mm

Advertisement

loading

Summary of Contents for Siemens 5SD7 483-3

  • Page 1 5SD7 483-3 / 5SD7 483-4 MLFB 5SD7 483-3 / 5SD7 483-4 Montageanleitung Anforderungsklasse / Requirement class C acc. to E DIN VDE 0675-6; Installation Instruction SPD class II acc. to IEC 61643-1; SPD Type 2 acc. to EN 61643-11 Max. Stringspannung U...
  • Page 2 Al abrir el aparato se pierde cualquier derecho de garantía frente al fabricante. Aviso: los protectores de sobrecarga 5SD7 483-3 y 5SD7 483-4 están previstos para el montaje aislado en una carcasa. Entre las partes activas y puestas a tierra debe man- tenerse una distancia lateral y en la zona de conexión de al menos 8 mm.