CHAPTER 4 COMMISSIONING OF A STANDALONE SYSTEM SETUP

FIGURE 4-1
Part No.: 4417584_Rev12
Commissioning of a Standalone System Setup
Perform the following steps to commission a standalone CIU 888
system setup:
1. Log on to the CIU 888 and changing the initial password, see section
4.2.1
2. Verify the CIU 888 license, see section 4.2.2
3. Configure the site using Service Tool, see section 4.3
4. Send the site configuration to the CIU 888, see section 4.4
5. Generate the INI files, see section 4.5
6. Start the Entis Pro system connected to the CIU 888, and loading the
INI files in Entis Pro, see section
7. Verify the CIU 888 system setup is working properly, see section
4.10
8. Seal the CIU 888, see section 4.11
4.1 Requirements for commissioning
For the commissioning of a standalone CIU 888 system setup the
following requirements must be met:
The electrical and mechanical installation of the CIU 888 must be
completed. Refer to the Installation Manual CIU 888 (Part No.
4417590) for more information.
The CIU 888 must be switched on, see section 7.1.1
Both the W&M lock key switch and the Configuration lock key switch
must be in 'unlocked' position, see section 7.2
A PC/laptop running the CIU 888 Service Tool must be connected to
the Service port of the CIU 888 using a Cat. 5 Ethernet cable (patch
or crossover). The Service port is located at the front of the CIU 888
(see FIGURE 4-1). See Chapter 3 for more information about the
CIU 888 Service Tool.
CIU 888: Service port
Configuration Manual
CIU 888
4 - 1