1 Engineering SINAMICS S120 Booksize
Converter connection at the low-voltage line supply:
Inductance value per unit length of the converter connecting cable according to data sheet information
L'
FC line
Cable length to the converter
l
FC line
-
Specific resistance of the converter connecting cable
ρ
FC
-
Cross-section of one phase of the converter connection
q
FC
Minimum relative short-circuit power for the type of infeed corresponding to
RSC
min
Rated input current of the Line Module for a 380 V line supply voltage
I
rated_Line_Module
Rated power of the Line Module for the selected supply voltage
P
rated_Line_Module
k factor – takes into account the supplementary losses in the transformer due to harmonic currents - for Booksize Line Modules, k = 1.27
k
infeed
11
This value is very dependent on the geometrical structure of the cable and/or the conductor. The following approximate values can be used if more precise data are not available:
µ��
0.25
for cables and conductors,
��
µ��
0.38
for busbars,
��
12
specific resistances of copper, aluminum and aluminum alloy
2
1
����
Ω
for copper
54
��
2
1
����
Ω
for aluminum
34
��
2
1
����
Ω
for aluminum alloy
31
��
Engineering manual S120 Booksize
Entry-ID: 109808992,
V1.0,
04/2022
© Siemens AG 2022 All rights reserved
µ��
=
0.2550
��
35.0
=
m
12
��
����
��
=
0.01852
��
=
75.0
mm²
=
30
192
=
A
120
=
kW
=
1.27
11
Table 1-1