(b) Locations without special precautions to minimize the presence of sand or dust. Also applies to locations in close
proximity to sand or dust sources.

5. Quick start up

5.1. Step 1: Visual and installation check

Upon reception of the equipment, make sure that
– The packing is in good condition.
– For PQFI/M filters, verify the state of the shock and tilting indicators (if mounted on the enclosure).
– After removal of the packing, check visually the exterior and interior of your filter for transportation damage.
– Your filter equipment comes with an information package that is present in a documentation holder attached at
each filter panel. Verify that all documentation is present, i.e.:
• this quick start manual in printed version and the detailed manuals in a CD-ROM
• the electrical drawing and connection diagram
• the communication cable needed for multi-unit operation
Any loss or damage should be notified immediately to your HITACHI ENERGY representative.
WARNING: Make sure that the filter is installed at a location where no conductive dust is present. Conductive
dust when distributed in the filter panel may lead to equipment failure.
– Check that the mechanical and electrical installation fulfills the requirements. Check for the following:
• Cable size. These are typical cables for some of the common filter ratings. Different combinations of cables
are also possible; please refer to the detailed manuals for more information.
Filter type
PQFS 30-100A
PQFS 120A
PQFM 100A
PQFM 150A
PQFI 180A
PQFI 300-320A
PQFI 450A
• Ambient temperature (below 40°C) and altitude (≤ 1000m). Use suitable derating in case these limits are ex-
ceeded.
• Upstream protection is adequately provided.
– Remove the anti-corrosion capsules which are affixed at the inside of the filter, at the bottom (next to the fan and
IGBT assembly) for the PQFS and at the top inside the door for the PQFI and PQFM.
STATUS
Approved
Table 13: Cable size selection table for 50 Hz
Cross section of cables [mm²] (copper cable without shielding)
16
25
16
35
50
150
2 x 120
SECURITY LEVEL
Public
DOCUMENT ID
9AKK107045A4703
Q UICK STA RT-UP G UI DE
REV.
LANG.
PAGE
D
en
22/41
© 2022 Hitachi Energy. All rights reserved.