Transport And Handling; By Receiving Inspection; Storage - ABB SafeRing Product Manual

Table of Contents

Advertisement

Max angle 60
o

3. TRANSPORT AND HANDLING

The units are delivered from the factory ready for installation.
Weight table
Maximum weights for standard SafeRing
2-way DeV
300 kg
3-way CCV
450 kg
4-way CCCV
600 kg
4-way CCVV
600 kg
3-way CCC
450 kg
4-way CCCC
600 kg
SafePlus
Standard 1-way
2-, 3- and 4-way
5-way
M - metering module incl. trafo
Mt - metering tariff module incl. trafo
The weights are without additional equipment, except for
transformers for M- and Mt-modules
SafeRing / SafePlus is fitted with lifting lugs, but can also be
moved on a pallet with a forklift truck. Make sure to secure
the switchgear.
NOTE:
Use only approved slings when lifting.
Maximum angle on lifting lugs is set to 60

3.1 BY RECEIVING INSPECTION

Upon receiving the SafeRing / SafePlus please check that the
delivered equipment has not been damaged during transport.
If any such damage has occurred, a claim must be submitted
to the carrier immediately.
After unpacking, the following must be checked:
1. Operating handle – one piece should be included, normally
fixed on right-hand side.
2. Check that the pointer on the pressure indicator is in the
green area.
3. Carry out a function test on the mechanical parts.
4. Visual check of the switchgear.
Any faults or omissions must be reported immediately to
the supplier.

3.2 STORAGE

SafeRing / SafePlus must be stored under cover in a dry and
well ventilated area until it is installed and put into operation.
2-way DeF
300 kg
3-way CCF
450 kg
4-way CCCF
600 kg
4-way CCFF
600 kg
150 kg
as for SafeRing
750 kg
250 kg
350 kg
.
o
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Safeplus

Table of Contents