Download Print this page

Hitachi P1 VFD Installation And Manual page 27

Advertisement

Parameter
Name
Function code
B037
display
restriction
Frequency
A001
Source
Run Command
A002
Source
F002
Acceleration time
(1)
F003
Deceleration
time (1)
A003
Base Frequency
A004
Maximum
Frequency
A082
Motor Voltage
b012
Level of
electronic
thermal
H004
Poles
Definition
Default Value
Unlock All
4
Parameters
Options for
frequency
command:
Control = 1,
2
ModBus = 3,
Option card = 4,
etc. 
Options for run
2
command source
Standard default
10
acceleration,
range is 0.01 to
3600 sec.
Standard default
10
deceleration,
range is 0.01 to
3600 sec.
Settable from 30
60
Hz to the
maximum
frequency(A004)
Settable from the
60
base frequency
to 400 Hz
Settable from the
2nd base
frequency to 400
Hz
200V class: 200 /
215 / 220 / 230 /
240 VAC
200
400V class: 380 /
400 / 415 / 440 /
460 / 480 VAC
Set a level
Rated Current
between 20%
and 100% for the
rated inverter
current.
4
Units
Change Value
0
Opt.
1
1
sec
3
Sec
3
Hz
300
Hz
300
volts
220
A
100%
2

Advertisement

loading

This manual is also suitable for:

Wj200