RA-100 Remote Annunciator Installation
Wiring Distance Calculation Example:
Suppose a system is configured with the following SBUS modules:
2 - RA-1000 Fire Annunciators
1 - 5496 Intelligent Power Expander
1 - 5865 LED Fire Annunciator
1 - 5824 Parallel/Serial Interface
The total worst case current is calculated as follows:
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
•
370 feet maximum using 22 Gauge wire
•
938 feet maximum using 18 Gauge wire
•
1493 feet maximum using 16 Gauge wire
•
2,362 feet maximum using 14 Gauge wire
4.6.3 Wiring Configurations
Figure 4.11 illustrates SBUS, Class B configuration.
4.7 RA-100 Remote Annunciator Installation
The optional model RA-100 Remote Annunciator, is shown in Figure 4.12. The RA-100 can be surface or flush mounted. Up to 16 annunci-
ators can be added to the IFP-300 system in any combination.
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Wire Gauge
22
18
16
14
Table 4.5 Typical Wire Resistance Per 1000 ft.
RA-1000 Current Draw
RPS-1000 Current Draw
5865 Current Draw
5824 Current Draw
Total Worst Case Current Draw
Table 4.6 Worst Case Current Draw
FACP
Figure 4.11 SBUS Class B Wiring
Ohms per 1000 feet (Rpu)
16.2
6.4
4.02
2.54
= 2 x 0.100 amps
= 0.200 amps
= 1 x .010 amps
= .010 amps
= 1 x 0.200 amps
= 0.200 amps
= 1 x 0.040 amps
= 0.040 amps
= 0.450 amps
supervised,
power-limited,
Class B
Control Panel Installation
B
A
SBUS device
+
-