23
3.3.5 Specification
Items
Output Specification
Outputs Per Module
Indicators(Logic side)
Resolution in Ranges
Output Range
Data Format
Module Error
Load Resistance
Diagnostic
Conversion Time
Calibration
Common Type
General Specification
Power Dissipation
Isolation
UL Field Power
Field Power
Wiring
Torque
Weight
Module Size
Environment Condition
Specification
8 Channels Single Ended, Non-Isolated Between Channel
8 Green Output Status
12 Bit: 2.44mV/Bit
0 ~ 10Vdc
16 Bits Integer (2' complement)
±0.1% Full Scale @ 25℃
±0.3% Full Scale @ -40℃ ~ 70℃
Min. 2KΩ
Field Power Off: LED Blinking
Field Power On: No Output LED Off
Field Power On: Output LED ON
0.2msec / All Channel
Not Required
2 Common, Field Power 0V is Common (AGND)
Max. 30mA @ 5.0Vdc
I/O to Logic: Isolation
Field Power: Non-Isolation
Supply Voltage: 24Vdc nominal, Class 2
Supply Voltage: 24Vdc nominal
Voltage Range: 18~30Vdc
Power Dissipation: Max. 70mA @ 24Vdc
2
I/O Cable Max. 2.0mm
0.8Nm (7lb-in)
58g
12mm x 99mm x 70mm
Refer to 'Environment Specification'
HX-RIO3 Series
(AWG 14)