(b) Grounding the twisted pair cable
• Always use shielded twisted pair cables for connection to
10BASE-T and 100BASE-TX connectors.
For the shielded twisted pair cable, strip a part of the jacket
as shown below and ground the exposed shield section in
the largest possible area.
(c) Grounding the CC-Link Ver. 1.10 compatible cable
Be sure to ground the cable shield that is connected to the CC-
Link module close to the exit of control panel or to any of the
CC-Link stations within 30cm from the module or stations.
• The CC-Link Ver. 1.10 compatible cable is a shielded cable.
Strip a part of the jacket as shown below and ground the
exposed shield section in the largest possible area.
Always use the specified CC-Link Ver. 1.10 compatible cable.
Connect the CC-Link module and the CC-Link stations to the
FG line inside the control panel at the FG terminal as shown
below.
Master module
(Blue)
DA
DA
Terminating
(White)
resistor
DB
DB
(Yellow)
DG
DG
SLD
SLD
FG
FG
Shielded twisted pair cable
Shield
CC-Link Ver.1.10 compatible cable
Shield
Remote module
(Blue)
DA
DA
(White)
DB
DB
(Yellow)
DG
DG
SLD
SLD
CC-Link Ver.1.10
compatible cable
FG
FG
46
(Blue)
(Blue)
(White)
(White)
(Yellow)
(Yellow)
CC-Link Ver.1.10
compatible cable
Local module
DA
DA
Terminating
resistor
DB
DB
DG
DG
SLD
SLD
FG
FG