a) If the DDC can provide 0-10V, mode and on/off signals to Haier AHU kit, the wired controller does not need to be
connected. If only 0-10V signal, the wired controller is necessary.
b) If Haier wired controller is connected into the system, the wired controller has the top priority. As a result, if the
wired controller is set into off status, signals from DDC to Haier AHU kit will be invalid. When the wired controller
is turned on, first to adjust operation mode and then the 3rd party AHU units can be controlled by 0-10V signal
from DDC to Haier AHU kit adjusting the outdoor unit capacity.
c) If the wired controller is connected, wired controller can directly control the 3rd party AHU fan motor. Or Haier
AHU kit PCB provides fan speed dry contact signal to DDC or to AHU unit PCB directly. If users want to use
wired controller to adjust fan speeds, set the wired controller according to AHU fan motor grades and max. 3 fan
speeds can be controllable.
d) Haier AHU kit can provide mode signal to DDC or AHU unit PCB directly to control the AHU unit, e.g. if the DDC
or 3rd party AHU unit PCB receives defrost signal from AHU kit, AHU fan motor will be controlled.
e) The maximum input range of voltage whitch is from DDC is 0-10v. If it exceeds 10V, input shall be 10V; if it is
lower than 0V, input shall be 0V. The maximum input voltage shall not exceed 10V.
• Plan B: Setting temperature by 0-10V signal.
Simple DDC Voltage Range(V)
0~1.0
1.1~1.7
1.8~2.3
2.4~2.9
3~3.5
3.6~4.1
4.2~4.7
4.8~5.3
5.4~5.9
6~6.5
6.6~7.1
7.2~7.7
7.8~8.3
8.4~8.9
9~10
a) If the DDC can provide 0-10V, mode and on/off signals to Haier AHU kit, the wired controller does not need to be
connected. If only 0-10V signal, the wired controller is necessary.
b) If Haier wired controller is connected into the system, the wired controller has the top priority. As a result, if the
wired controller is set into off status, signals from DDC to Haier AHU kit will be invalid. When the wired controller
is turned on, first to adjust operation mode and then the 3rd party AHU units can be controlled by 0-10V signal
from DDC to Haier AHU kit adjusting the outdoor unit capacity.
c) If the wired controller is connected, wired controller can directly control the 3rd party AHU fan motor. Or Haier
AHU kit PCB provides fan speed dry contact signal to DDC or to AHU unit PCB directly. If users want to use
wired controller to adjust fan speeds, set the wired controller according to AHU fan motor grades and max. 3 fan
speeds can be controllable.
d) Haier AHU kit can provide mode signal to DDC or AHU unit PCB directly to control the AHU unit, e.g. if the DDC
or 3rd party AHU unit PCB receives defrost signal from AHU kit, AHU fan motor will be controlled.
e) The maximum input range of voltage whitch is from DDC is 0-10v. If it exceeds 10V, input shall be 10V; if it is
lower than 0V, input shall be 0V. The maximum input voltage shall not exceed 10V.
Set Temperature(°C)
Cool
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
33
Heat
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30