Download Print this page

Toshiba TCB-LD1UPE Installation & Operation Manual page 4

Leak detector

Advertisement

Gases and vapours other than the target refrigerant gas, may cause semi-conductor
sensors to react.
Sensors exposed to silicon fumes may be permanently damaged. The accumulation of
volatile organic compounds resulting from human occupation in a poorly ventilated room
may cause inaccurate operation.
Adequate room ventilation should be maintained at all times.
Ground yourself to discharge static electricity before performing any wiring.
Do not install the Leak Detector in places with direct sunlight or where the ambient
temperature is more than 40°C or is less than 0°C. Follow 2.Specification
The connecting cable must not touch piping directly.
Install this Leak Detector horizontally.
The warranty does not cover the product if it falls from an elevated location.
Do not use the Leak Detector at the following locations. Because may lead to severe
decrease in functionality and damage to parts.
• Location where condensation occurs
• Location where flammable gases, etc. may leak
• Location where corrosive gases, etc. may leak
• Location with lots of water or oil droplets (including machine oil)
• Steamy locations
• Location where voltage fluctuation frequently occurs
• Location where there is a machine producing electromagnetic radiation
• Location where droplets of organic solvents spread
• Location where acidic or alkaline solutions or special sprays are frequently used
• Locations where dust easily accumulates or Extremely dusty
The semi-conductor sensor may react or malfunction if exposed to gases other than the
refrigerant gas or to steam. Accordingly, the following must be avoided when installing.
• Using in atmospheres where silicone gases (siloxane, etc.) may occur
The Leak Detector may malfunction or operate incorrectly if items such as adhesives,
hair products, rubbers, or putties with silicone in them are used in the vicinity of the
Leak Detector.
• Exposing to organic solvents/chloric gases Alcohols, VOCs, Chloric gases, etc., can be
the cause of malfunction or incorrect operation. Large amounts of organic solvents are
produced by paints, floor waxes, etc., when building or renovating structures, so
ensure the area is properly dried and ventilated before installing the Leak Detector.
• Polluting with alkaline metals (especially salt mist)
3-EN
CAUTION
3