Fujitsu ARU7RLF Service Instruction page 67

Slim duct / compact cassette compact wall mounted / wall mounted / floor
Hide thumbs Also See for ARU7RLF:
Table of Contents

Advertisement

Trouble shooting 28
OUTDOOR UNIT Error Method:
Discharge Temp. Error
Detective Actuators:
Outdoor unit Main PCB
Discharge temperature thermistor
Forecast of Cause :
1. 3-way valve not opened
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor failure
6. Main PCB failure
<Cooling operation>
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
Check Point 2 : Check the EEV, strainer
EEV open?
Strainer clogging check
Strainer clogging check
(Refer to PARTS INFORMATION 3)
(Refer to PARTS INFORMATION 3)
OK
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check (PARTS INFORMATION 5)
OK
Check Point 4 : Check the discharge thermistor
Discharger thermistor characteristics check.
(Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 16".
OK
Check Point 5 : Check the refrigerant amount
Leak check
Indicate or Display:
Refer to error code table.
Detective details:
"Protection stop by "discharge temperature
°F(36
239
type) during compressor operation"" generated 2 times
within 24 hours.
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
Check Point 2 : Check the EEV, strainer
EEV open?
Strainer clogging check
(Refer to PARTS INFORMATION 3)
OK
02-32
°F
230
(18/24type) /
2. EEV defective, strainer clogged
5. Insufficient refrigerant
OK