Mitsubishi Electric 800 Series Instruction Manual page 15

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Output signal
Terminal
Type
Common
symbol
A, B,
Relay
*1*3
C
*1
SE
RUN
Open
collector
*1
SE
FU
Pulse
FM
SD
*1
Terminal functions can be selected using Pr.190 to Pr.192 (Output terminal function selection). (Refer to the FR-E800 Instruction
Manual (Function).)
*2
The open collector transistor is ON (conductive) in LOW state. The transistor is OFF (not conductive) in HIGH state.
*3
To comply with the Low Voltage Directive (conforming standard EN 61800-5-1) and UL or cUL standards (conforming standard UL 61800-
5-1), the operating capacity of the relay outputs (terminal symbols A, B, and C) should be 30 VDC, 0.3 A. (Relay output has basic isolation
from the inverter internal circuit.)
Terminal name
1 changeover contact output that indicates that an
inverter's protective function has been activated
Relay output (fault
and the outputs are stopped.
output)
Fault: discontinuity across B and C (continuity
across A and C), Normal: continuity across B and
C (discontinuity across A and C)
The output is in LOW state when the inverter
output frequency is equal to or higher than the
starting frequency (initial value: 0.5 Hz). The
Inverter running
output is in HIGH state during stop or DC injection
brake operation.
The output is in LOW state when the inverter
output frequency is equal to or higher than the
preset detection frequency, and is in HIGH state
Frequency detection
when it is less than the preset detection
frequency.
Among several monitor
items such as output
frequency, select one to
output it via this terminals.
(The signal is not output
For meter
during an inverter reset.)
The size of output signal is
proportional to the
magnitude of the
corresponding monitor item.
Terminal function description
*2
*2
Output item:
Output frequency
(initial setting)
PRE-OPERATION INSTRUCTIONS
Rated specification
Contact capacity: 230
VAC 0.3 A (power factor
= 0.4)
30 VDC 0.3 A
Permissible load: 24
VDC
(27 VDC at maximum)
0.1 A
(The voltage drop is 3.4
V at maximum while the
signal is ON.)
Permissible load current:
1 mA
1440 pulses/s at 60 Hz
15
1