Advertisement

4350
Multi detector
B
In the detector:
A
Contact for base 2324
B
Contact for base 2324
The detector is plugged in a base 2324.
Voltage (V DC)
rated
allowed
normal
Current consumption at nom. volt.
(mA)
quiescent (detector only)
active (detector only)
Ambient temperature (°C)
operating
storage
Ambient humidity (% RH)
Ingress Protection rating (estimated)
Sensitivity (obscuration; %/m)
Sensitivity (T=°C; deltaT=
Size ∅ x h (mm)
Weight (g)
Construction / Colour
Approvals
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
MEW00309
Type number
The zone line is connected to the base 2324 (A-B)
Ext. LED is connected to the base 2324 (A-L).
A
Technical data
24
12-30
24
Depending on the base the detector is plugged into. For more details see
the Product Leaflet respectively, e.g. MEW00008 (Base 2324).
0.04
min. 3
-10 to +50
-25 to +75
max. 95, non condensing
IP 51
3.7 / 5 (depending on algorithm)
>2.5 in combination with temp. rate-of-rise (depending on algorithm)
°
57; 6.43 / not used (depending on algorithm)
C/min.)
57; >1.07 in combination with smoke obscur. (depending on algorithm)
102 x 46
84
Modified polycarbonate / Grey (N8, Munsell colour code)
05 EC Certificate no. 0786-CPD-20143; EN54-7
Date of issue
2002-12-03
See also "Engineering Instructions for detectors Type 435x".
Revision / Date of revision
5 / 2006-08-31

Advertisement