Mitsubishi Electric FR-A802-P Instruction Manual page 44

Separated converter type for parallel operation
Table of Contents

Advertisement

Safety stop signal
Terminal
Terminal name
symbol
Safety stop input
S1
(Channel 1)
Safety stop input
S2
(Channel 2)
Safety stop input
SIC
terminal common
Safety monitor output
So (SO)
(open collector output)
Safety monitor output
SOC
terminal common
Terminal function description
Terminals S1 and S2 are used for the safety stop input signal for
the safety relay module. Terminals S1 and S2 are used at the
same time (dual channel).
Inverter output is shutoff by shortening/opening between
terminals S1 and SIC, or between S2 and SIC.
In the initial status, terminals S1 and S2 are shorted with
terminal PC by shorting wires. Terminal SIC is shorted with
terminal SD. Remove the shorting wires and connect the safety
relay module when using the safety stop function.
Common terminal for terminals S1 and S2.
Indicates the safety stop input signal status.
Switched to LOW when the status is other than the internal
safety circuit failure. Switched to HIGH during the internal safety
circuit failure status.
(LOW is when the open collector output transistor is ON
(conducted). HIGH is when the transistor is OFF (not
conducted).)
Refer to the Safety Stop Function Instruction Manual when the
signal is switched to HIGH while both terminals S1 and S2 are
open. (Please contact your sales representative for the manual.)
Common terminal for terminal So (SO).
Control circuit
Rated
specification
Input resistance 4.7
k
Input current 4 to 6
mADC (with 24 VDC
input)
Permissible load
24 VDC (27 VDC at
maximum), 0.1 A
(The voltage drop is
3.4 V at maximum
while the signal is
ON.)