Beko BEKOMAT 14 CV Instructions For Installation And Operation Manual page 28

Table of Contents

Advertisement

Elektrische Installation • Instalación eléctrica
Installazione elettrica • Instalação eléctrica
C
H
K
28
A
B
E
F
D
VAC - voltages
2.2
IN1
ext. Test
*)
2.3
0V
0V
0.8
normally open
0.7
common
0.6
normally closed
0.2
PE
Earth/Ground
0.1
N
Neutral
0.0
L
Phase
24 VDC - voltage
2.2
IN1
ext. Test
*)
2.3
0V
0V
0.8
normally open
0.7
common
0.6
normally closed
6
±24V +24 VDC (0V)
5
±24V 0V (+24 VDC)
english
• It is imperative to read the permissible
mains voltage from the type plate (G)!
• Carry out installation works in accor-
dance with VDE 0100 / IEC 60364.
• Do not install when voltage is applied.
• Lift off domed cover (A) after removing
the 4 screws (B).
• Take power supply board (C) out of the
domed cover (A) after removing the
screw (D).
• Guide cables for power supply (E)
and potential-free contact (F) through
screwed cable fittings.
• Terminals
VAC power supply 0.0 L
0.1 N
0.2 PE
24 VDC power supply +24 VDC (0V)
0V (+24 VDC)
In the case of 24 VDC operation, do
not connect +24 VDC to frame because
the internal housing potential of the
device is negative.
The provided 24 VDC voltage must meet
the requirements for protective extra-low
voltages (PELV) in accordance with IEC
60364-4-41.
• Connect potential-free contact (F) to
terminals 0.6 - 0.7 (fail safe) or 0.7 - 0.8
(open during malfunction).
• Pull cable (E + F) tight and screw down
cable fittings.
• Screw power supply board (G) with
screw (D) into domed cover (A)
• Plug ribbon cable (H) into control PCB
(K)
• If the individual wires have not been
screwed into the plug, they should be
attached as follows: 1.0 = brown
1.1 = blue
2.0 = black
• Put on top of cover (A) and tighten the
4 screws (B)
External Test
see page 14-15
*) 0...1 V Test activ
5...36 V Test inactiv
Please note:
The power supply board (C) is in a
reverse position (upside down) in the
domed cover (A).
During no-load operation, a voltage of up
to 36 VDC may be measured at terminals
1.0 and 1.1 (plug ribbon cable (H)).
BEKOMAT 14 CV, 14 CO CV

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bekomat 14 co cvBm14cvBm14cocv

Table of Contents