INSTALLING THE BREAKER:
12a. Orient the breaker such that the "ON"-side (with Bus
Extensions, part of Item 15) fits into the Top Barrier
(Item 4) and the "OFF"-side nestles between the
two fins on the Breaker Mounting Bracket (Item 5).
12b. Fasten the breaker to the Breaker Mounting Bracket
(Item 5) with two #8-32 screws (part of Item 15).
(NOTE: Some breakers are packaged with a pair
of Breaker-Mounting Screws. If this occurs, dispose
of the pair that shipped with the breaker and use the
pair from this kit.)
12c. Align the Bus Extension (part of Item 15) holes with
the holes in the Straps (Items 1, 2 and 3) and fasten
with one 5/16"-18 screw (part of Item 15) per phase.
15
15
Figure 13
12d. If installing two breakers in the same unit space,
repeat the three steps above.
12e. Keeping components aligned, tighten all screws to
the torque values specified on the back of the
deadfront (or the table on Page 2).
INSTALLING THE NEUTRALS:
13a. If this kit is installed in a panelboard with a neutral,
install the Branch Neutral Lug Assembly (Item 13).
Locate on the Branch Neutral at either the top or
bottom of the Z-rails. Lug can be mounted on either
side of the Branch Neutral, depending on cable feed
location.
13
Figure 14
13b. If this kit is installed in a switchboard with a neutral,
install the Branch Neutral Lug Assembly (Item 14).
It can be mounted as shown or on any available
hole of the branch neutral, depending on cable feed
location.
These instructions do not purport to cover all details or variations in equipment, or to provide for every possible contingency
to be met in connection with installation, operation or maintenance. Should further information be desired or should particular
problems arise, which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the local
Siemens sales office. The contents of this Instruction manual shall not become part of or modify any prior or existing
agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens. The warranty
contained in the contract between the parties is the sole warranty of Siemens. Any statements contained herein do not
create new warranties or modify the existing warranty.
Trademarks - Unless otherwise noted, all names identified by ® are registered trademarks of Siemens AG or Siemens
Industry, Inc. The remaining trademarks in this publication may be trademarks whose use by third parties for their own
purposes could violate the rights of the owner.
Figure 15
14
13c. Keeping components aligned, tighten all screws to
the torque values specified on the back of the
deadfront (or the table on Page 2).
DEADFRONT PREPARATION:
NOTE: Provision Filler Assembly (Item 16) not a
component of kits KS3VA52T or KS3VA52TD. Skip 14a.
14a. If a provision is in place, install the Provision Filler
Assembly (Item 16) in the appropriate Cover Plate
(Item 6) opening. Place a screw into each of the two
corner square holes and locate the filler plate onto
the front of the Cover Plate, with the label facing out.
Then, fasten two lock nuts onto the screws from the
rear of the Cover Plate.
6
7
16
Figure 16
10
11
14b. Position the Cover Plate (Item 6) over the five inch
unit space and fasten with four 1/4"-20 screws
(Item 7) onto the deadfront rails, one at each corner.
14c. Mark the I.D. cards (Item 11) as desired and place
onto the rear of Card Holder (Item 10), with the
marking facing out. Attach this subassembly to the
Cover Plate (Item 6) by aligning and pushing the
pins into the appropriate pair of holes in the Cover
Plate (Item 6).
FINAL PREPARATION:
15.
Before energizing the equipment, ensure that
the deadfront, barriers and fillers are in place and
secure, and that all the covers are properly installed.
-4-
s
Distribution Switchboard Section /
Power Panel Branch Mounting Kit
S3VA52T / S3VA52TD
for Type 3VA52 / 61 / 62 Breaker
Hardware Key:
(based on what is included in this kit)
Item # 7
Item # 9 (reference instruction sheet 11-B-1009-01)
Item numbers reference table on pg. 2
For factory-installed provisions, verify that the strap kit contains
bus extensions. (See Figure 12 on page 3 for reference.)
If bus extensions are not included, kit S3VA52PR is required,
one kit per breaker. Consult Siemens for more details.
*
This instruction sheet can also be used as reference for
these two Panel Builder kits: KS3VA52T & KS3VA52TD
These two kits will ship with all the same components as kits
S3VA52T & S3VA52TD except for:
nut keepers & provision filler plate assemblies
Nut keepers must be purchased with the breaker. Order options are:
for 3VA52 breakers:
for 3VA61/62 breakers: 3VA9243-0QA00 (kit of 3)
or factory-installed on the breaker by using a "2" as the 12th
character in the breaker order: ( Ex.: 3VA61405HL320AA0 )
Additionally, when installing a factory-installed provision,
nut keepers must be purchased with the breaker
Installation
*
Instructions
Item # 8
3VA9233-0QA00 (kit of 3)
11-A-1168-01 Rev. 02

Advertisement

loading

Summary of Contents for Siemens S3VA52T

  • Page 1 Siemens sales office. The contents of this Instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens. The warranty Additionally, when installing a factory-installed provision, contained in the contract between the parties is the sole warranty of Siemens.
  • Page 2 THREE-PHASE (3Ø) SYSTEM PREPARATION: 8b. Repeat Step 8a to attach a pair of A/C-phase straps The following instructions are for the installation of a Siemens 3VA branch breaker kit for 250A MAX 3VA52 (MFAS, to the C-phase bus. 7a. Fasten the B-phase strap (Item 1) to the B-phase bus, HFAS, CFAS), 150A MAX 3VA61 (MDAE, HDAE, CDAE, LDAE) or 250A MAX 3VA62 (MFAE, HFAE, CFAE, LFAE) vertically centered in the 5”...

This manual is also suitable for:

S3va52td