Flush mount room temperature sensor

Advertisement

Quick Links

MANUFACTURED FOR:
MITSUBISHI ELECTRIC US, INC.
Flush Mount Room Temperature Sensor
PAC-USSEN002-FM-1
INSTALLATION/INSTRUCTION MANUAL
For your safety, first be sure to read 1.Safety Instructions and then
install the Flush Mount Room Temperature Sensor
PAC-USSEN002-FM-1 correctly.
Contents
1. Safety Instructions
2. Confirming the Supplied Parts
3. Mounting Instructions
4. Troubleshooting
5. Setting Indoor Units
6. Thermistor Calibration Table
1. Safety Instructions
This sensor is not polarity sensitive and includes 24" of 22/2 AWG (ETFE) stranded
etched Teflon wires for making all of the proper connections. Mitsubishi Electric US,
Inc. recommends using 22/2 AWG UL 1007 non-shielded wire for up to 100' with this
application. Temperature measurement range: 41° to +140˚ F (5° to +60˚ C)
This symbol denotes what could lead to serious injury or death if
Warning
your misuse the PAC-USSEN002-FM-1.
This symbol denotes what could lead to a personal
injury or damage to your property if you misuse the
Caution
PAC-USSEN002-FM-1.
After reading this installation manual, keep it in a place where the final user can see
it anytime he or she wants to.
When someone moves, repairs or uses the PAC-USSEN002-FM-1, make sure that
this manual is forwarded to the final user.
Do not install in any place exposed to
flammable gas leakage.
Flammable gases accumulated around the
body of PAC-USSEN002-FM-1 may cause
an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including
machine oil), steam and sulfuric gas may
deteriorate the performance significantly or
give damage to the component parts.
Wire so that it does not receive any
tension.
Tension may cause wire breakage, heating
or fire.
Completely seal the wire lead-in port
with putty, etc.
Any dew, moisture, cockroaches or insects
entering the unit may cause an electric
shock or malfunction.
Do not wash with water.
Doing so may cause an electric shock or a
malfunction.
2. Confirming the Supplied Parts
Confirm that following parts are enclosed
in the box in addition to this installation
manual.
• Flush mount sensor
• Threaded insert
• Noise filter board with CN20
connector
• Instruction sheet
Specifications are subject to change without notice.
FOR INSTALLER
CAUTION
Do not install in any place where an
acidic or alkaline solution or special
spray are often used.
Doing so may cause an electric shock
or malfunction.
Use standard wires in compliance
with the current capacity.
A failure to do this may result in an
electric leakage, heating or fire.
Do not install in a place with much
steam such as bathroom or kitchen.
Avoid any place where moisture is
condensed into dew.
Doing so may cause an electric shock
or a malfunction.
Do not touch any PCB (printed
circuit board) with your hands or
with tools. Do not allow dust to
collect on the PCB.
Doing so may cause a fire or an
electric shock.
Do not install in any place at a
temperature of more than 40° C or
less than 0° C or exposed to direct
sunlight.
ATTENTION
PAC-USSEN002-FM-1 does not
come with the conversion cable
and is not compatible with the
following indoor units: PEFY-NMHU,
PFFY-NEMU and PFFY-NRMU.
Ask your dealer or technical
representative to install the unit.
Any deficiency caused by your installation
may result in an electric shock or fire.
Install in a place which is strong
enough to withstand the weight of the
PAC-USSEN002-FM-1.
Any lack of strength may cause the
PAC-USSEN002-FM-1 to fall down,
resulting in personal injury.
Firmly connect the wiring using the
specified cables. Carefully check that
the cables do not exert any force on
the terminals.
Improper wiring connections may produce
heat and possibly a fire.
Never modify or repair the
PAC-USSEN002-FM 1 by yourself.
Any deficiency caused by your
modification or repair may result in an
electric shock or fire. Consult with your
dealer about repairs.
3. Mounting Instructions
1. Select location for installation.
• Select a place where the sensor will detect an average temperature of the
room.
• Make sure that the sensor is not in direct sunlight, miscellaneous heat
sources, drafts, outside wall or supply air from the unit itself. These may
generate incorrect readings.
• Drill or cut open a hole into the wall where the sensor will be installed. For
hollow walls, the hole should be ½".
• Mount the sensor with the threaded insert inside of this hole by turning it
clockwise until it sits flush with the wall.
• When mounting into solid walls (i.e. marble or rock) a ¼" hole is
recommended, and the threaded corkscrew insert is not required.
• Field wire must be provided on site.
2. Connect the wires.
• Connect the sensor wires to the field wires using crimp connectors or wire
nuts.
• Connect the loose end of the field wires to the wires extending from the noise
filter board.
• Connect CN20 connector from the noise filter board to CN20 on the indoor
unit control board.
WARNING
Ensure that installation work
is done correctly following this
installation manual.
Any deficiency caused by
installation may result in an electric
shock or fire.
All electrical work must be
performed by a licensed
technician, according to local
regulations and the instructions
given in this manual.
Any lack of electric circuit or any
deficiency caused by installation
may result in an electric shock
or fire.
Do not move and re-install the
PAC-USSEN002-FM-1 yourself.
Any deficiency caused by
installation may result in an electric
shock or fire.
Ask your dealer for moving and
installation.
Do not turn on the main power
until installation has been
completed.
Failure to do so may cause an
electric shock or fire.
© 2022 Mitsubishi Electric US, Inc.

Advertisement

loading

Summary of Contents for Mitsubishi Electric PAC-USSEN002-FM-1

  • Page 1 This sensor is not polarity sensitive and includes 24” of 22/2 AWG (ETFE) stranded Never modify or repair the Do not turn on the main power etched Teflon wires for making all of the proper connections. Mitsubishi Electric US, PAC-USSEN002-FM 1 by yourself. until installation has been Inc.
  • Page 2 982.82 1584.04 955.32 1535.43 928.74 1488.58 903.04 Manufactured for: 1443.43 878.19 MITSUBISHI ELECTRIC US, INC. 1399.91 www.mitsubishielectric-usa.com Toll Free: 800-433-4822 MEUS DOC# MD-2222-K001, Ver. 1, April 2022 Specifications are subject to change without notice. © 2022 Mitsubishi Electric US, Inc.