There are three different methods to achieve this aim.
Method A: Cutting JP001 to ignore capacity
One possibility is to cut jumper JP001 on the outdoor unit main PCB.
i
Important
Method A is only applicable to the following combinations of PACi outdoor units and AHU Kits:
● PACi PEY/PE outdoor units (R410A) and PAH2/PAH3 AHU Kit models
● PACi PZ2/PZH2 outdoor units (R32) and PAH2/PAH3 AHU Kit models
To cut jumper JP001 on the PACi outdoor unit main PCB, complete the following steps:
1. On the PACi outdoor unit PCB, cut the wire of jumper JP001 at two positions, and take the cut
jumper leads off. Depending on the PACi outdoor unit model, it can be found on the main PCB
at one of the following positions:
Standard –
U-60PEY2E5
U-71PEY2E5
Standard –
U-60PZ2E5
U-71PZ2E5
JP001
Standard –
U-100PZ2E5
U-125PZ2E5
U-140PZ2E5
AHU Kit – Installation Instructions – 11/2021
JP001
R410A
Elite –
R410A
U-36PE2E5A
U-50PE2E5A
U-60PE2E5A
R32
Elite –
R32
U-36PZH2E5
U-50PZH2E5
U-60PZH2E5
R32
Standard –
R410A
Elite –
R410A
U-100PEY1E5
U-71PE1E5A
U-125PEY1E5
U-100PE1E5A
U-100PEY1E8
U-125PE1E5A
U-125PEY1E8
U-140PE1E5A
U-140PEY1E8
U-71PE1E8A
U-100PE1E8A
U-125PE1E8A
U-140PE1E8A
JP001
Elite –
R32
U-71PZH2E5
U-100PZH2E5
U-125PZH2E5
U-140PZH2E5
Installation
JP001
Standard –
R32
Elite –
U-100PZ2E8
U-200PE2E8A
U-125PZ2E8
U-250PE2E8A
U-140PZ2E8
Elite –
U-200PZH2E8
U-250PZH2E8
JP001
Elite –
U-71PZH2E8
U-100PZH2E8
U-125PZH2E8
U-140PZH2E8
JP001
R410A
R32
R32