Blinking Inspection Display - Panasonic U-10MF1E8 Service Manual

3-way system
Hide thumbs Also See for U-10MF1E8:
Table of Contents

Advertisement

4. 3-WAY ECO-i Alarm Codes

5. Blinking Inspection Display

P29 Alarm
Alarm code
P29
Alarm meaning
Inverter compressor missing phase or lock alarm
Alarm conditions
This alarm may occur at start, and occurs when missing phase or lock is detected, and when a
DCCT failure occurs.
Probable cause
Generally this alarm occurs when the refrigerant pressure balance is uneven at start, or when
inverter compressor lock occurs, there is a missing phase in the inverter compressor wiring, or a
DCCT failure occurs. This can be judged to be starting trouble which is not caused by HIC.
Check
Check the power wiring and connector wiring.
Correction
DCCT failure (replace PCB) or compressor failure
Example
Notes
Use a tester to measure the voltage between the DCCT output terminal on the rear of the PCB
and the ground. If the voltage is not within 2 – 3 V, then the DCCT has malfunctioned.
Currently the blinking inspection display can be displayed only on the wired remote controller
CAUTION
and system remote controller.
Blinking inspection display (1) (Automatic backup)
Alarm code

(Blinking inspection display)

Alarm meaning
Automatic backup is in progress. A/C units can be operated.
Status: The compressor at one of the outdoor units where the outdoor unit fan is running should
Alarm conditions
When alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, correcting the control device
(remote controller, etc.) input engages this mode.
Probable cause
Because alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, check the alarm history
then refer to the corresponding items.
Correction
Follow the instructions in the corresponding items to correct the trouble.
Recovery
After repairing the malfunctioning locations, reset the power for the system (all outdoor units).
Caution: Automatic backup mode will not be canceled until the power is reset.
Notes
Automatic backup mode is not engaged in cases of alarms other than those listed above.
Reasons: • There is no need for automatic backup if recovery is possible by correcting the
be operating.
* Blinking inspection display also occurs when seizing of the compressor magnet SW
is detected. Because this may also be the case, refer to "Blinking inspection display
(compressor magnet SW seizing detection)."
remote controller input.
• With alarms for which automatic recovery is possible (such as sensor alarms), the
presence of electrical noise may result in a new alarm. However, it is believed that
this occurs for a comparatively short time only. In these cases, a mode (automatic
backup mode) that limits operation may be engaged.
• Control is not possible when a communications system alarm has occurred.
Automatic backup mode is not engaged in order to avoid causing secondary
damage.
5 - 27
3-WAY SYSTEM
Trouble Diagnosis
5