GE D400 Substation Data Manager User Manual page 26

Table of Contents

Advertisement

GE Energy
3.2
Changing Card Settings
The communication cards are factory installed with default settings. You may want to
adjust individual card settings to work with your specific system set up. The
communication cards are hot swappable -- this means you do not have to power down
the D400 unit to remove and install the communication cards.
»
To change the settings on a communication card:
At the rear panel of the D400, using a flathead or Phillips screwdriver loosen (but
1.
don't completely remove) the two screws from the top and bottom of the
communication card.
Using the flathead screwdriver, gently pry the top of the card from the slot and
2.
remove it from the chassis.
Refer to the instructions in the following sections to make any required changes to
3.
the switch settings on the card.
Tip: Use a small flathead screwdriver (same as used to remove the communication
card screws) to change switch positions.
Slide the card into the same slot you removed it from, and tighten the two screws.
4.
CAUTION: For proper transient protection, the recommended tool torque settings for
communication card screws are 2.6 in-lb [0.294 Nm].