LMV52... with MM440 Variable Speed Drive
User Documentation
Building Technologies Division
CC1A7550.2en
Industry Sector
20.05.2011

Advertisement

loading

Summary of Contents for Siemens LMV52 Series

  • Page 1 LMV52… with MM440 Variable Speed Drive User Documentation Building Technologies Division CC1A7550.2en Industry Sector 20.05.2011...
  • Page 2 2/10 Building Technologies Division LMV52… with MM440 Variable Speed Drive CC1A7550.2en Industry Sector 20.05.2011...
  • Page 3: Table Of Contents

    The following MM440 parameters are required to be entered......5 2.1.1 Perform quick commissioning................5 LMV5… section ....................8 Electrical connection between LMV5… and Siemens MM440 Variable Speed Drive ........................ 8 The following LMV52… parameters must be entered ........9 3/10 Building Technologies Division LMV52…...
  • Page 4: Safety Notes

    Safety notes It is important to read the Siemens «Micromaster 440 Operating Instructions» (6SE6400-5AW00-0BP0) and ensure the MM440 is correctly installed complying with appropriate Regulatory Authorities before attempting to commission the MM440 Vari- able Speed Drive. For more detailed information, refer to the relevant Data Sheet (N7550) and the Basic Documentation (P7550).
  • Page 5: Parameters

    Parameters 2.1 The following MM440 parameters are required to be entered The table below describes the functions of the key pad (BOP / AOP) on the front of the MM440 Variable Speed Drive to enable the parameters to be entered. The LCD displays the settings Indicates This button is disabled by default...
  • Page 6 Parameter Setting Description End quick commissioning with motor calculation and End quick commissioning P3900 factory reset (recommended) Note: It is recommended to set «P3900 = 1» for «End quick commissioning» After performing quick commissioning continue with entering the following MM440 parameters. Parameter level access P0003 Expert level 3...
  • Page 7 Parameter Setting Description Motor temp. sensor P0601 PTC thermistor (check motor sensor for compatibility) Motor temp. reaction P0610 Warning, no reaction, trip F0011 (default) Activate «AOP» to automatically display run screen Upon powering up the Variable Speed Drive with AOP, perform the following: Simultaneously press <Fn>...
  • Page 8: Lmv5

    LMV5… section 3.1 Electrical connection between LMV5… and Siemens MM440 Variable Speed Drive Note: Ensure the speed feedback sensor «AGG5.310» has been installed correctly on the motor ac- cording to Mounting Instructions «M7550» and the LMV5... Basic Documentation (P7550en). 8/10 Building Technologies Division LMV52…...
  • Page 9: The Following Lmv52

    3.2 The following LMV52… parameters must be entered Menu level 1 - enter on «Params & Display» Enter on «Access OEM» the password START - then press «Enter» again to access OEM parameters Activating Variable Speed Drive (VSD) Menu level 2 - enter on «RatioControl» Menu level 3 - enter on «GasSettings»...
  • Page 10 Siemens AG Industry Sector Building Technologies Division © 2011 Siemens AG Industry Sector Building Technologies Division Berliner Ring 23 Subject to change! D-76437 Rastatt Tel. +49 7222 598 279 Fax +49 7222 598 269 www.sbt.siemens.com 10/10 Building Technologies Division LMV52… with MM440 Variable Speed Drive CC1A7550.2en...