Electrical Data For Inputs And Outputs - ABB EBN861 Operating Instruction

Hide thumbs Also See for EBN861:
Table of Contents

Advertisement

EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C

Electrical data for inputs and outputs

Power supply
EBN853
Supply voltage (standard actuators)
Supply voltage (Ex actuators)
Current consumption at the electronic unit
(AC 115 V / AC 230 V)
External fuse for electronic unit
EBN861
Supply voltage (standard actuators)
Supply voltage (Ex actuators)
Current consumption at the electronic unit
(AC 230 V)
External fuse for electronic unit
115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase
115 V AC (94 to 127 V) or 230 V AC (190 to 253 V); 47.5 to 63 Hz; single-phase
Actuator
l
at 115 V
max
RHD(E)250-10
1.8 A
RHD(E)500-10
2.2 A
RHD(E)800-10
5.0 A
RHD(E)1250-12
5.0 A
RHD(E)2500-25
5.0 A
RHD(E)4000-40
5.8 A
RHD(E)8000-80
5.0 A
RSD(E)10-5,0
2.2 A
RSD(E)10-10,0
3.6 A
RSD(E)20-5,0
3.6 A
RSD(E)20-7,5
4.8 A
RSD(E)50-3,0
5.0 A
RSD100-1.5
5.0 A
RSD200-0.7
5.0 A
16 A; time-lag
230 V AC (190 to 260 V); 47.5 63 Hz; single-phase
230 V AC (190 to 253 V); 47.5 63 Hz; single-phase
Actuator
l
at 230 V
max
RHD(E)2500-10
5.3 A
RHD(E)4000-10
10.0 A
RHD8000-12
8.0 A
RHDE8000-15
8.0 A
RHD(E)16000-30
12.5 A
RSD(E)50-10
6.4 A
RSD100-10.0
12.5 A
RSD200-5.0
13.0 A
Safety fuse 35 A (Lindner) + thermal circuit breaker 16 A (ETA); fuses are in the scope of delivery
l
at 230 V
l
(115 V + 230 V):
max
pos
approx. 40 to 50 % of l
0.9 A
1.1 A
2.5 A
2.5 A
2.5 A
2.7 A
2.5 A
1.1 A
1.8 A
1.8 A
2.4 A
2.5 A
2.5 A
2.5 A
l
(230 V): approx. 40 to 50 % of l
pos
27
max
max

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebn853