12.8. DC Fan motor (FAN MOTOR/INDOOR CONTROLLER BOARD)

Check method of DC fan motor (fan motor/indoor controller circuit board)
12-8. DC FAN MOTOR (FAN MOTOR/INDOOR CONTROLLER BOARD)
Notes
1
· High voltage is applied to the connecter (CNMF) for the fan motor. Give attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on.
(It causes trouble of the indoor controller circuit
2
Self check
Symptom : The indoor fan cannot turn around.
Check the fuse (FUSE) on indoor
controller board.
Did the fuse blow?
Yes
No
Wiring contact check
Contact of fan motor connector (CNMF)
No
Is there no contact failure?
Yes
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
TEST POINT
1 : V
(between 1 (+) and 4 (-) of the fan connector): V
DC
TEST POINT
2 : V
(between 5 (+) and 4 (-) of the fan connector): V
CC
Is the voltage normal?
Yes
No
Replace indoor
controller board.
OK
Check the operation.
END
NG
Replace the fan motor.
SVZ-KP-NA
Measuring points
Resistance
pin 1 - pin 4
O.L.
pin 5 - pin 4
50kΩ
pin 6 - pin 4
150kΩ
pin 7 - pin 4
O.L.
*To measure the resistance, connect
the negative (-) end of the tester to pin 4.
Specifications are subject to change without notice.
NTXAMT12, 18, 24, 30, 36A112AA
board and fan motor.)
Check the drain pump (DP)
Is the resistance between
terminals normal?
No
Replace drain pump (DP).
Wiring recovery
board.
DC310~340V
DC
DC15V
CC
Measure the resistance of the fan motor.
No
Is the resistance of the fan motor
normal?(Refer to below table)
Yes
No
Does the fan motor rotate smoothly?
Yes
Turn OFF the power supply and
connect the connector CNMF.
Turn ON the power supply and
measure the voltage of connector
CNMF while rotaing the motor by
the hand.
Does the voltage between pin 7 and pin 4
of connector CNMF repeat 0V and 5V?
Yes
OK
Check the operation of fan.
END
NG
Replace indoor controller board.
55
Replace indoor controller board (I.B).
Yes
Replace fan motor (MF).
Replace the fan motor.
No
Yes
Check the operation of fan.
NG
Replace indoor controller board.