Beko BM13CV Instructions For Installation And Operation Manual page 14

Condensate drain
Table of Contents

Advertisement

Function • Funcionamiento
Functionnement • Funcionamento
1
3
Switching sequence of valve in alarm mode
Secuencia de actuación de la válvula en el modo de alarma
Séquence d'activation de la vanne en mode Alarme
Sequência de ligação da válvula no modo de alarme
Alarm signal via potential-free contact
Mensaje de alarma a través de contacto sin potencial
Signal d'alarme délivré sur le contact sans potentiel
Sinal de alarme via contacto isento de potencial
14
2
4
english
Ready for operation
1
Voltage is being applied
Discharge procedure
2
Outlet line is open
Malfunction
3
Alarm mode is activated
Test
4
Manual drainage/alarm
The test button is used for checking
correct functioning.
Pressing
Effect
Short
Manual drainage
> 1 min
Alarm mode
Compared with BEKOMAT 13 standard
types, the alarm mode of the BEKOMAT
13 CV is different. By an altered opening
sequence on alarm, a significantly larger
condensate quantity may be discharged,
this enabling the reduction of a conden-
sate backup during the state of alarm.
When the microcontroller registers a
malfunction, the device will automatically
change to the alarm mode. The switching
sequence of the valve (see illustration)
continues until the fault is cleared (auto-
matically or through maintenance). The
red LED flashes as long as the device is
in the alarm mode.
Malfunctioning could be caused by, e.g.:
• Mistakes during installation
• Dropping below the necessary mini-
mum pressure
• Excessive condensate quantities
(overloading)
• Blocked/shut off outlet line
• Extreme amount of dirt particles
• Frozen piping
If the fault is not cleared within the first
minute, a fault signal is triggered (see
illustration) which can be picked off as a
potential-free signal via the alarm relay.
BEKOMAT 13 CV, 13 CO CV

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bekomat 13 co cvBekomat 13 cvBm13cocv

Table of Contents