Vn unit heater controls

Advertisement

DN code Configuration
Connect a remote controller and set the DN codes as required. To access the
DN codes Press the Test Set and Cl. You can then press the temperature up
and down arrows to select the code to be modified. Once the selected code
has been updated press the SET button to register the change and then the
Spanner button to exit.
THESE CONFIGERATION CODES MUST BE SET
FAILURE TO DO THIS COULD RESULT IN BUILDING DAMAGE
Set DN Code 67 to the required on temperature.
Set DN Code 68 to the required heater operation time.
Heater Operation
When the unit air on sensor in the unit reaches the value set in (Table 1) the
heater will be enabled. The heater will operate for the time set in (Table 2) at
the end of this time the heater will switch off. If the unit air on value is still
below the set value in Table 1 the process stars again. if it is above the heater
remains OFF. Should the temperature significantly rise the heater will turn off.
If the unit is switched off on the remote controller the fan will run on for approximately
30s.