Example 2
START
Emergency
stop button
+24V
X0
COM0
X1
COM1
Internal
DC24V
Safety
Circuit
24G
MITSUBISHI ELECTRIC
MELSEC Safety relay module
QS90SR2SN-Q
Fig.6 Safety system example 2 – STOP synchronous with emergency stop button and fault
NOTE
XS0 should be connected to RUN terminal and XS1 should be connected to SE, because polarity of
XS0 is positive, XS1 is negative.
Pr. 190 (RUN terminal function selection) must be set to "81". This setting makes the RUN output to
turn off in case of failure.
The above wiring is configured to prevent restart in case of a fault.
When starting up the system's operation, press the START switch to reset the safety stop function
first, then turn ON the STF switch to run the motor.
In the above Fig.6, wired example 2, in the event of reset of 'safe-condition' the motor rotation will
not occur until STF is pressed.
(for normal 'non-safety' STF/STOP function, please refer to your drive's User Manual)
 To prevent restart in case of recovering from input power loss of drive, 3-wired connection for
STF/STOP control is recommended. In case of 2-wire connection and using latching type switch to short
between STF and SD/PC for starting, ensure the compliance with safety requirement for the restarting
when the drive recover from input power loss.
Inverter connection
Do not connect the FR-E700-SC/NF/NC (source logic) or the FR-D700-SC (source logic) together with the
FR-D700 (sink logic). If connected together, the safety stop function does not work properly.
FR-E700-SC/NF/NC
(source logic)
FR-D700-SC
(source logic)
FR-D700 (sink logic)
RUN (SAFE2)
STF
STOP
XS0
XS1
Z00
Z10
Z20
K1
K2
Z01
Z11
Z21
* If the control logic is SINK logic, the common
terminal is terminal SD.
detection through RUN output.
FR-E700-SC/NF/NC
(source logic)
SE
STF
STOP
CPU
+24V
S1
+24V
S2
SC
PC*
CAUTION
FR-D700-SC
(source logic)
8
R/L1 S/L2 T/L3
IGBTs
Gate
Gate
Driver
Driver
G
G
U
V
FR-D700
M
FR-D700 (sink logic)
: Enabled,
: Disabled
W