3.3

Code input example

The following table explains examples of terminal status and input value during BCD code input and binary input.
BCD code input (when the input value is 6325)
Terminal
Digit
Terminal input status
name
X0
ON
X1
OFF
1
X2
ON
X3
OFF
X4
OFF
X5
ON
10
X6
OFF
X7
OFF
X8
ON
X9
ON
100
X10
OFF
X11
OFF
X12
OFF
X13
ON
1000
X14
ON
X15
OFF
NOTE
• For BCD code input, the input value of each digit is from 0 to 9. When a value greater than 9 is input, it becomes invalid and
the last value is retained.
• When Pr.304 Digital input and analog input compensation enable/disable selection = "0 to 4", X12 to X15 become
disabled.
22
16-BIT DIGITAL INPUT
Binary input (when the input value is HAB65)
Terminal
Input value
name
X0
X1
5
X2
X3
X4
X5
2
X6
X7
X8
X9
3
X10
X11
X12
X13
6
X14
X15
Terminal input
Input value
status
(hexadecimal)
ON
OFF
5
ON
OFF
OFF
ON
6
ON
OFF
ON
ON
B
OFF
ON
OFF
ON
A
OFF
ON
Input value
(decimal)
43877