Outputting separate signals from terminals AM0 and AM1 (Pr.309 = "1 or 11")
START
Connect a DC voltmeter (or DC ammeter)
across terminals AM0 (or terminal AM1) and AMC.
Use Pr.323 (or Pr.324) to calibrate the meter
when the voltage (current) input is 0.
Set "21" (reference voltage output) in Pr.306
and Pr.310.
Terminal AM0
Use C0 (Pr.900) to set
END *1
*1
In Pr.306 and Pr.310, set the types of the signals to be output. (Refer to
NOTE
• If calibration is performed without setting "21 (reference voltage output)" in Pr.306 or Pr.310, terminal FM, CA, or AM of the
inverter is calibrated. To calibrate the extended analog output, always set to "21".
• When the plug-in option used was remounted on another inverter, use Pr.323 and Pr.324 to calibrate again.
At this time, check that the polarity is correct.
If the meter needle does not indicate zero when the voltage or current
input is at zero, calibrate the meter using Pr.323 AM0 0 V adjustment
or Pr.324 AM1 0 mA adjustment.
At this time, the following analog signal is actually output and deflects the meter.
<Across terminals AM0 and AMC>
Maximum output voltage set previously (factory setting: 10 VDC)
<Across terminals AM1 and AMC>
Maximum output current set previously (factory setting: 20 mADC)
Terminal AM1
After making adjustment with
Use C1 (Pr.901) to set
press
to deflect the meter to full-scale,
to set.
page
28.)
ANALOG OUTPUT