8.2.4

Replacing the Motor Limit Switch and/or the Auxiliary Switch

REV7
/REV2
• Disconnect the wire connections to the motor limit switch (7) and/
or the auxiliary switch (5).
6
3
1
Lever
2
Drive rod
3
Locking clamp
4
Connecting rod
5
Auxiliary switch
6
Drive rod
7
Motor limit switch
• Remove the locking clamps (3). Remove the drive rod
(2 or 6) and the connecting rod (4).
• Unscrew the M5 mounting screws.
• Remove the motor limit switch or auxiliary switch.
• Unscrew the M4 screw(s) and remove the lever (1).
• Mount the lever on the new motor limit switch or auxiliary switch.
OI 250 (EN)
T
ROUBLESHOOTING
1 2
5
7
1
3
4
-
-
-
-
-
-
-
69 / 146