Panasonic U-8LE1R8 Installation Instructions Manual page 61

Hide thumbs Also See for U-8LE1R8:
Table of Contents

Advertisement

ATTENTION!
Adjustment of terminating resistance (pin) is necessary.
Communication failure will occur unless adjustment is made correctly.
• • Terminating resistance (pin) is mounted on outdoor unit control P.C. board.
• • When connecting central controller, interface or peripheral equipment, adjustment of terminating resistance (pin) is necessary.
Although the connection is not made, confirmation is necessary for VRF systems.
• • In the case of a refrigerant system, the terminating resistance (pin) for this inter-unit control wiring (S-LINK wiring) is one
location (See the section "7-4. Auto Address Setting").
For 2 or more refrigerant systems, 2 locations should be valid ("SHORT" for VRF systems at shipment). See the section
"7-4. Auto Address Setting".
In order to make 2 locations valid, let the terminating resistance (pin) of the nearest outdoor unit and the farthest outdoor unit be
valid (SHORT side) from the location of central controller.
In other refrigerant systems excepting 2 locations described above, make them invalid (OPEN side).
It is prohibited making more than 3 locations of terminating resistance valid.
• • Since the use of linking the sub outdoor units of VRF systems is not connected to the inter-unit control wiring, it is not necessary
to make the terminating resistance invalid "OPEN side".
Make fi nal confi rmation regarding the central controller or interface & inter-unit control wiring (S-LINK wiring) connected to the
peripheral equipment.
Measure the line resistance with a tester and check whether the values are in the range of 30Ω - 120Ω.
If the resistance values are out of range, check again the terminating resistance.
Nevertheless, if the values are out of range, the problem comes from wiring.
• • Is the connection properly made?
• • Are there any scratches or damages on the coated surface?
• • Measure the line, between wires and ground with the 500V megger (insulation
resistance meter) and check the values are over 100MΩ.
• • When measuring, be sure to remove both edges of the wire from the terminal board.
If not removed, it will be damaged.
• • If the line resistance is within 100MΩ, newly carry out the wiring work.
61
Megger
Line
(Wire)
(Wire)
Between wires and ground
(Wire)
(Wire)
(Ground)

Advertisement

Table of Contents
loading

Table of Contents