AIR CONDITIONER (MULTI TYPE)
Installation Manual
Indoor Unit
Model Name:
High-Wall Type
MMK-UP0271HP-E
MMK-UP0301HP-E
MMK-UP0361HP-E
Scan QR CODE to access installation and owner's manual on website.
https://www.toshiba-carrier.co.th/manuals/default.aspx
Manual are available in AR/BG/CZ/DA/DE/EL/EN/ES/ET/FI/FR/
HR/HU/IT/LT/LV/NL/NO/PL/PT/RO/RU/SK/SL/SV/TR.
For commercial use
Installation Manual
1130550112A
English
1

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba MMK-UP0271HP-E

  • Page 1 AIR CONDITIONER (MULTI TYPE) Installation Manual Indoor Unit For commercial use Model Name: High-Wall Type MMK-UP0271HP-E MMK-UP0301HP-E MMK-UP0361HP-E Scan QR CODE to access installation and owner’s manual on website. https://www.toshiba-carrier.co.th/manuals/default.aspx Manual are available in AR/BG/CZ/DA/DE/EL/EN/ES/ET/FI/FR/ HR/HU/IT/LT/LV/NL/NO/PL/PT/RO/RU/SK/SL/SV/TR. English Installation Manual 1130550112A...
  • Page 2: Table Of Contents

    Installation Manual Original instruction Please read this Installation Manual carefully before installing the Air Conditioner. This Manual describes the installation method of the indoor unit. For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit. For precaution for safety, follow the Installation Manual attached to the outdoor unit.
  • Page 3: Accessory Parts

    Installation Manual ACCESSORY PARTS Part name Q’ty Shape Usage Installation Manual This manual For hand over to customers Owner’s Manual For hand over to customers Installation plate Wireless remote controller Battery Remote controller holder Mounting screw Ø4 × 25 Flat head wood screw Ø3.1 × 16 Screw Ø4 ×...
  • Page 4: Selection Of Installation Place

    Installation Manual SELECTION OF INSTALLATION PLACE WARNING Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. CAUTION When an outdoor unit using R32 refrigerant is combined with indoor unit, be attention to the For details, follow the Installation Manual to the outdoor unit.
  • Page 5 Installation Manual Installation diagram of Indoor unit For the rear left, bottom left and left piping Packing material Wall Split Hook Installation plate SPACER Hook Split out 2 pieces of SPACER from indoor unit packing material, insert between the indoor unit and wall to tilt the indoor unit for better operation.
  • Page 6 Installation Manual CAUTION • Direct sunlight to the indoor unit’s wireless receiver should be avoided. • The microprocessor in the indoor unit should not be too close to RF noise sources. (For details, see the owner’s manual.) Wireless remote controller •...
  • Page 7: Installation Of Indoor Unit

    Installation Manual INSTALLATION OF INDOOR UNIT WARNING An incomplete installation can cause accidents by the units falling and dropping. REQUIREMENT Strictly comply with the following rules to prevent damage of the indoor units and human injury. Do not put a heavy article on the indoor unit. (Even units are packaged) Carry in the indoor unit as it is packaged if possible.
  • Page 8: Cutting A Hole And Mounting Installation Plate

    Installation Manual CUTTING A HOLE AND MOUNTING INSTALLATION PLATE Cutting a hole When the installation plate is directly mounted on the wall In case of installing the refrigerant pipes from the rear: by screwing it in the upper and lower parts to Decide the hole position for piping at hook up the indoor unit.
  • Page 9: Piping And Drain Hose Installation

    Installation Manual PIPING AND DRAIN HOSE INSTALLATION Piping and drain hose forming * Since dewing results in a machine trouble, make sure to insulate both connecting pipes. (Use polyethylene foam as insulating material.) Rear right Rear left Bottom left Left Bottom right Right 1.
  • Page 10 Installation Manual Clip the drain cap by needle-nose pliers and pull out. Drain cap Drain cap 2) Firmly insert drains cap. Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap. Application causes deterioration and drain leakage from the plug. No gap wrench (4 mm) CAUTION...
  • Page 11 Installation Manual In case of bottom right or bottom left piping • After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an equivalent tool. Slit Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
  • Page 12 Installation Manual Gas side Heat insulator provided Indoor unit shield pipe Liquid side Cut the heat insulator of the gas pipe (locally procured) leaving a 10 mm overlap with the shield of the shield pipe. Make the slit part of heat insulator to upward. Insulate the indoor unit completely so there are no gaps using the heat insulator provided.
  • Page 13: Indoor Unit Fixing

    Installation Manual INDOOR UNIT FIXING DRAINAGE 1. Pass the pipe through the hole in the wall, and 1. Run the drain hose sloped downwards. hook the indoor unit on the installation plate at NOTE the upper hooks. Hole should be made at a slight downward slant on the outdoor side.
  • Page 14: Refrigerant Piping

    Installation Manual REFRIGERANT PIPING Permissible Piping Length and CAUTION Height Difference Use flare nuts that are included with the unit. They vary according to the outdoor unit. Using different flare nuts may cause refrigerant For details, refer to the Installation Manual gas leakage.
  • Page 15 Installation Manual CAUTION • Do not scratch the inner surface of the flared the nut depending on installation conditions. part when removing burrs. Tighten the nut within the specified tightening • Flare processing under the condition of torque. scratches on the inner surface of flare processing part will cause refrigerant gas leak.
  • Page 16 Installation Manual Wireless remote controller A-B unit selection Open the valve of the outdoor unit fully. Using 2 wireless remote controllers for the respective air conditioners, when the 2 air valve. conditioners are closely installed. For details, refer to the Installation Manual attached to the outdoor unit.
  • Page 17: Electrical Connection

    Installation Manual ELECTRICAL CONNECTION WARNING REQUIREMENT For power supply wiring, strictly conform to the Local Regulation in each country. external tension to the wires do not affect For wiring of power supply of the outdoor the connecting part of the terminals. units, follow the Installation Manual of each outdoor unit.
  • Page 18 Installation Manual Power supply wire and communication wires are procured locally. wiring are to be procured locally. Installation Manual supplied with the outdoor unit. • • Arrange the power supplies to the indoor and outdoor units, so that a common earth leakage breaker and main switch can be used.
  • Page 19 Installation Manual line and Uc line 0.5 mm² (Up to 500 m) Wire size : (2-core shield wire, non-polarity) 0.75 to 1.25 mm² (Up to 1000 m) Uh line (L1) 0.75 to 1.25 mm² (Up to 1000 m) Wire size : (2-core shield wire, non-polarity) 2.0 mm²...
  • Page 20 Installation Manual Control wiring between indoor units, and outdoor unit (2-core shield wire, non-polarity) 1.25 mm² (Up to 1000 m) Wire size : 2.0 mm² (Up to 2000 m) Central control line wiring (L1) (2-core shield wire, non-polarity) Control wiring between outdoor units (L4) Wire size : 1.25 to 2.0 mm²...
  • Page 21 Installation Manual Wired remote controller wiring This wiring is not required when using the supplied wireless remote controller. For wiring remote controllers a 2 core non polarity wire must be used. Wired remote controller wiring, remote controller inter-unit wiring Wire size: 0.5 mm² to 2.0 mm² In case of wired type only Up to 500 m Total wire length of wired remote controller wiring and remote...
  • Page 22 Installation Manual NOTE • outdoor unit series, refer to the Installation Manual attached to the outdoor unit to be connected. Wiring example Outdoor Power supply Outdoor Power supply Circuit breaker Circuit breaker Outdoor unit Outdoor unit Header outdoor Follower outdoor Earth Earth terminal...
  • Page 23 Installation Manual Wiring Connection Power supply terminal block Terminal block for communication/remote controller wiring The power supply wire and the control wire can be Screw connected without removing the front panel. Terminal cover Earth screw Connect the power supply wire after connecting Clamp base Screw the control wire for this model.
  • Page 24 Installation Manual indoor unit. 1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you. 2. Remove the terminal cover and the clamp base. 3. Insert the control wire fully into the control/wired remote controller terminal block and secure it tightly with screws.
  • Page 25: Applicable Controls

    Installation Manual APPLICABLE CONTROLS REQUIREMENT time, it will take some moments after the power has been turned on before the remote controller becomes available for operations: This is normal and is not indicative of trouble. Concerning the automatic addresses (The automatic addresses are set up by performing operations on the outdoor interface circuit board.) While the automatic addresses are being set...
  • Page 26 Installation Manual sign [ ] [ ] setting button. According to the installation condition, the lighting Push OFF timer button. can be changed. Follow to the basic operation procedure To change other settings of the selected • indoor unit, repeat from Procedure •...
  • Page 27 Installation Manual Adjustment of air direction 1. Using the remote controller switch, change the up/down air direction by moving the horizontal louver. vertical grille inside of the air outlet port with hands. Do not touch the horizontal louver directly with hands;...
  • Page 28: Test Run

    Installation Manual TEST RUN Before test run Before turning on the circuit breaker, carry out the following procedure. 1) By using insulation tester (5 L to N and the earth (grounding). not run the unit. 2) Check the valve of the outdoor unit being opened fully.
  • Page 29 Installation Manual Wired remote controller (Forced test operation is performed in a Be sure to stop the air conditioner before (Change the setup while the air conditioner is not working.) • For the operation procedure, be sure to follow the Owner’s Manual. •...
  • Page 30: Troubleshooting

    Installation Manual TROUBLESHOOTING A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Con rmation and check If a problem occurs with the air conditioner, the OFF timer indicator alternately shows the check code and the indoor Unit No.
  • Page 31 Installation Manual On the remote controller (Wired remote controller, Central control remote controller) and the interface P.C. Board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. Board) to display the operation is provided. Therefore the operation status can be known.
  • Page 32 Installation Manual Wireless remote controller Wired Judging Outdoor unit 7-segment display remote controller Auxiliary code Operation Timer Ready Flash display Communication trouble between — — Indoor unit header and follower units Indoor unit 00: Header is not detected 02: Two or more header Outdoor header units quantity trouble units 01: Outdoor unit of other...
  • Page 33 Installation Manual Wireless remote controller Wired Judging Outdoor unit 7-segment display remote controller Auxiliary code Operation Timer Ready Flash display 1 * : Comp. 1 side Current detect circuit system trouble Inverter 2 * : Comp. 2 side — Comp. 1 case thermostat operation —...
  • Page 34 Installation Manual Wireless remote controller Wired Judging Outdoor unit 7-segment display remote controller Auxiliary code Operation Timer Ready Flash display L13 Detected indoor unit address Safety device setting unmatch L14 Detected indoor unit address Safety device nonconformity — Outdoor unit type mismatch trouble L18 Detected indoor unit address Flow Selector unit trouble —...
  • Page 35 Installation Manual Comp. Fan Inverter Inverter Trouble Comp. 1 Comp. 2 Comp. 1 + Comp. 2 Fan 1 Comp. 1 + Fan 1 Comp. 2 + Fan 1 Comp. 1 + Comp. 2 + Fan 1 Fan 2 Comp. 1 + Fan 2 Comp.
  • Page 36: Specifications

    SPECIFICATIONS Sound power level (dBA) Model Weight (kg) Cooling Heating MMK-UP0271HP-E MMK-UP0301HP-E MMK-UP0361HP-E * Under 70 dBA NOTICE CODE Notice code is a function only in TC2U-Link communication. When the outdoor or indoor unit detects its conditions requiring caution or maintenance, this function notices you to check your units with the spanner mark (Notice code mark) on the wired remote controller or central controller display.
  • Page 37: Appendix

    Installation Manual APPENDIX Work instructions 5. When a commercially available dryer is attached to the existing pipes. The existing R22 and R410A piping can be reused There is the possibility that copper green rust for inverter R32 product installations. has been generated. 6.
  • Page 38 Installation Manual Existing pipes: Cannot be used. Are there scratches or dents on the existing pipes? Use new pipes. Is it possible to operate the existing air conditioner? After the existing air conditioner is operated in cooling mode for approx. 30 minutes or longer,* recover the refrigerant.
  • Page 39 Installation Manual Declaration of Conformity Manufacturer: Toshiba Carrier (Thailand) Co.,Ltd. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand TCF holder: TOSHIBA CARRIER EUROPE S.A.S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below:...
  • Page 40 Installation Manual Declaration of Conformity Manufacturer: Toshiba Carrier (Thailand) Co.,Ltd. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand TCF holder: TOSHIBA CARRIER UK LTD. Porsham Close Belliver Industrial Estate Roborough Plymouth Devon...
  • Page 41 Installation Manual WARNINGS ON REFRIGERANT LEAKAGE The room in which the air conditioner is to be installed The possible amount of leaked refrigerant gas in requires a design that in the event of refrigerant gas rooms A, B and C is 10 kg. The possible amount of leaked refrigerant gas in Refrigerant R32 rooms D, E and F is 15 kg.
  • Page 42 Installation Manual CONFIRMATION OF INDOOR UNIT SETUP Prior to delivery to the customer, check the address and setup of the indoor unit, which has been installed Copy this sheet according to the No. of the indoor units. If the installed system is a group control system, use this sheet by entering each line system into each Installation Manual attached to the other indoor units.
  • Page 43 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand...

This manual is also suitable for:

Mmk-up0301hp-eMmk-up0361hp-e